14
TECHNIC
AL SPECIFIC
ATIONS
FAN INPUT POWER
Input power (total) (W)
Air flow (max) (dm3/s)
SFP =
SFP rate (Specific Fan Power)
recommended value <1.8 (kW m
3
/s)
Volume flow rate
Power (W)
SUPPLY/EXTRACT AIR VOLUMES
Volume flow rate
(dm
3
/s)
Pressure loss in ducts. Total pressure (Pa)
extract air
supply air
41 %
33 %
50 %
55 %
66 %
75 %
100 %
14 %
4 %
22 %
50
100
150
200
250
300
350
0
10
20
30
40
60
70
80
90
100
SFP 1,0
50
36
72
108
0
144
180
216
252
288
324
360
SFP 1,5 SFP 1,8
m³/h
(l/s)
dm³/s
0
10
20
50
40
30
60
70
80
90
100
dm³/s
(l/s)
m³/h
36
72
108
0
144
180
216
252
288
324
360
4 %
14 %
22 %
33 %
41 %
50 %
55 %
66 %
75 %
100 %
50
100
150
200
250
0
TECHNICAL SPECIFICATIONS
Product title
Vallox 101 MV R
Vallox 101 MV L
Product number
4102189
4102197
Air volumes
Supply air
Extract air
90 dm
3
/s, 100 Pa
98 dm
3
/s, 100 Pa
Fans
Supply air
Extract air
0,115 kW 0,9 A EC
0,115 kW 0,9 A EC
Post-heating
Electrical resistor, 1500 W
Electrical connection
230 V, 50 Hz, 8,3 A power plug
Pre-heating
–
Enclosure protection class
IP 34
Additional heating
–
Heat recovery bypass
Automatic
Filters
Supply air
Extract air
ISO Coarse > 75 % + ISO ePM₁
ISO Coarse > 75 %
Specific energy consumption (SEC)
in a cold climate
in a temperate climate
A+
A
Operating efficiencies
Annual efficiency
Supply air efficiency
Specific Fan Power (SFP)
70 % A
82 %
1,0 kW (38 dm
3
/s) A
Dimensions
(w x h x d)
598 x 447 x 596 mm
Weight
50 kg
Sound power level in the supply air duct (one duct)
by octave band L
w
, dB
Sound power level in the extract air duct (one duct)
by octave band L
w
, dB
Adjustment position
Adjustment position
Adjustment position (%)
4
14
22
33
41
50
55
66
75
100
4
14
22
33
41
50
55
66
75
100
Air flow dm³/s
9
15
17
38
45
54
57
67
73
82
11
24
34
46
56
66
73
83
92
99
Air flow m³/h
31
54
61
136
162
193
206 243 264 296
41
88
123
164 200 237
261 299 329 357
Medium
frequency
of the
octave
band
Hz
63
56
58
63
67
70
72
75
77
79
80
62
53
56
58
61
64
67
68
70
71
125
52
62
63
65
67
69
71
74
76
78
52
58
58
61
64
67
69
70
73
74
250
44
52
57
64
70
66
70
71
72
74
35
45
50
57
60
60
62
62
62
63
500
40
49
53
58
61
64
65
69
71
74
27
34
40
44
48
51
53
55
57
62
1000
32
41
46
51
55
58
60
63
67
68
16
23
28
33
36
39
42
44
46
48
2000
24
34
40
47
51
55
57
61
63
65
14
17
23
29
32
36
38
41
43
44
4000
23
25
31
38
43
48
50
55
57
60
16
16
17
21
24
28
31
34
36
39
8000
21
21
23
30
35
41
44
51
53
56
20
20
20
20
20
21
22
24
26
29
L
W
, dB
58
64
67
71
74
75
78
80
82
84
62
59
61
64
67
69
72
73
75
77
L
WA
, dB (A)
41
50
54
60
64
65
67
70
73
75
39
43
45
50
54
55
57
58
59
62
Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Adjustment position / Air flows (supply/extract)
Adjustment position (%)
4
14
22
33
41
50
55
66
75
100
Air flow dm³/s
13/15
21/24
29/32
39/41
43/46
55/58
60/62
69/72
76/78
84/85
Air flow m³/h
47/54
76/86
104/115
140/148
155/166
198/209
216/223
248/259
274/281
302/306
L
pA
, dB (A)
21
26
30
36
38
42
43
46
48
50
SOUND VALUES