MAINTENANCE INSTRUCTIONS

Filters

S

A

B

C

D

Heat recovery cell

C

E

D

MAINTENANCE

Before starting maintenance operations

When you open the VALLOX 096 MC unit, the security switch (S) 

turns  voltage  off.  In  spite  of  this,  disconnect  the  plug  of  the  unit. 

Disconnect  the  plug  of  the  VALLOX  096  MC  unit  before  starting 

maintenance operations.

Filters

When the maintenance reminder gives an alarm, the cleanliness of 

the fi lters must be checked. Outdoor air is fi ltered in the unit with two 

kinds of fi lters. A coarse fi lter (A) fi lters off insects, heavy pollen and 

other dust. An F7 class fi ne fi lter (B) fi lters off fi ne dust invisible to the 

eye. Extract air is fi ltered with a coarse fi lter (C).
By using original Vallox fi lters you ensure good operation of the 

ventilation unit and the best fi ltering result. The replacement interval 

of fi lters depends on dust content in ambient air. It is recommended to 

replace fans in spring and autumn, but at least once a year.

Heat recovery cell

When  you  replace  the  fi lters,  you  are  also  advised  to  check  the 

cleanliness  of  the  heat  recovery  (HR)  cell  (D)  at  an  interval  of 

approximately every two years. The sealing ledge (E) above the 

HR cell must be pulled off in the direction shown by the arrow in the 

fi gure. When the sealing ledge has been removed, the HR cell can 

be pulled out of the unit. Note! The laminas of the HR cell are very 

thin and get easily damaged.
If the HR cell is dirty, wash it by putting it in a solution of water with 

washing-up liquid. Rinse the HR cell clean with a jet of water. When 

water has drained from between the laminas, you can push the HR 

cell back in place. Finally, push the sealing ledge in place.

Summary of Contents for 096 MC R

Page 1: ...ow L model unit Adjustment of supply air heating 12 SC controller Code 3721 Models VALLOX 096 MC R VALLOX 096 MC L Operating maintenance and technical instructions Electrical connection 230 V 50 Hz 5...

Page 2: ...peration in dwellings and detached houses The winter function parameters can be adjusted for extreme conditions such as a swimming bath but even then it is advisable to contact Vallox Maintenance Adju...

Page 3: ...he HR cell is faulty Check the sensor and conductors replace if needed 2 Extract air sensor is faulty Check the sensor and conductors replace if needed 3 Supply air sensor is faulty Check the sensor a...

Page 4: ...ed with a coarse filter C By using original Vallox filters you ensure good operation of the ventilation unit and the best filtering result The replacement interval of lters depends on dust content in...

Page 5: ...f the extract air duct G figure 1 and then remove the stopper screw from the lower edge of the duct After that the extract air duct comes out by turning and simultaneously pushing downwards gures 2 an...

Page 6: ...You can check it by pouring a little water in the tank Clean if needed Do not let water ow into electrical devices VALLOX We reserve the right to make changes without prior notice Extract air fan Cond...

Page 7: ...8V 4 5V 6 0V 7 0V 7 7V 9 0V 10 0V 11 35V 2 8V 4 5V 6 0V 7 0V 7 7V 9 0V 10 0V 11 35V Air flow dm3 s 10 6 25 2 38 1 46 6 53 8 65 6 72 9 76 0 12 0 27 6 36 7 44 2 50 5 61 0 70 4 76 4 Medium frequency of...

Page 8: ...o safety switch SLO Phase voltage to circuit board from safety switch SNO Zero voltage to circuit board from safety switch SFL Phase voltage to supply air fan SFN Zero voltage to supply air fan EFL Ph...

Page 9: ...hollow echoing dividing wall and on a bedroom wall because of sound conduction or prevent sound conduction Condensing water connections The delivery includes a water seal By connecting a pipe to the...

Page 10: ...into the thread bars and lift the ceiling mounting plate in place Then push a rubber damper and washer to each thread bar all the way into the cup of the plate and turn the nut Shorten the lower ends...

Page 11: ...supply air 978044 6 Filter stand supply air 3464400 7 F7 filter 978220 8 HR cell 933260 9 Upper support for HR cell 3467200 10 Filter stand extract air 3464500 11 G4 coarse filter extract air 978045...

Page 12: ...1 09 601ENG 5 11 2014 PDF...

Reviews: