USING THE UNIT

FIREPLACE SWITCH

A switch with timer functions can be connected to the unit. The switch stops the 

extract air fan when the fireplace is being used. NOTE! Starting up the extract 

air fan can reduce the draw of the fireplace! In winter, this can disturb the winter 

mode of the ventilation unit. The situation will return to normal soon after the 

fireplace mode is turned off.

ADJUSTING THE SUPPLY AND EXTRACT AIR 

RATIO 

This function might be needed when the air flows are adjusted at the valves 

during installation. The user does not need to adjust this function once 

the valves have been adjusted, and indeed should not adjust it at all. A 

potentiometer can be used to reduce the supply or extract air flow as required. 
When the potentiometer is set roughly in the centre position, neither the supply 

nor the extract air flow has been reduced. When the potentiometer is turned 

anti-clockwise, the supply air flow is reduced, and when the potentiometer is 

turned clockwise, the extract air flow is reduced.

The potentiometer for adjusting 

the supply and extract air flows

TROUBLESHOOTING

Flashing LED

Problem

Correction

1

NTC sensor of the supply air from the cell is faulty

Check the sensor and the wires, replace as required

2

NTC sensor of the extract air is faulty 

Check the sensor and the wires, replace as required

3

NTC sensor of the supply air is faulty 

Check the sensor and the wires, replace as required

4

NTC sensor of the exhaust air is faulty 

Check the sensor and the wires, replace as required

5

NTC sensor of the outdoor air is faulty 

Check the sensor and the wires, replace as required

6

The supply air fan has stopped. 

Check the wiring of the fan, replace the fan as required

7

The extract air fan has stopped. 

Check the wiring of the fan, replace the fan as required

8

EEPROM is faulty 

Replace the circuit board

Concealed installation 

of the fireplace switch (optional)

TROUBLESHOOTING TABLE

If the ventilation unit is affected by any of the errors listed in the table, the unit will report the error through the error relay, 

signal light, and circuit board LEDS. The number of flashes indicates the nature of the error.
The error relay can be connected to remote monitoring.  

NOTE! When remote monitoring is used, the signal light of the control panel cannot be turned on.

MAINTENANCE REMINDER

If a signal light is connected to the connectors of the unit’s error relay, the unit will send a reminder of service need every 

six months,. If connected, the signal light will flash every second. Sounds made by the relay can then be heard from 

inside the unit. The maintenance reminder will be set off automatically when the door of the ventilation unit is opened or 

the power is turned off. 
The maintenance reminder can also be set off manually.

The Vallox Simple Control panel, and the Vallox 

X-Line PTXP MC and PTXPA MC control hoods, 

VAK 0-10 VDC:

•  The low speed is turned on, then higher-lower-higher
  - Low speed under 4 V
  - High speed over 6 V
  - The selected speed will always be turned on for 1-5     

   seconds

Vallox Capto PTC EC control hood:

•  The damper is closed, then open-closed-open
•  Press at a 1-5 second interval.

The service reminder will only be set off if it has been activated. Refer to the maintenance instructions for the necessary 

maintenance measures.

Summary of Contents for 096 MC L

Page 1: ...Manual MANUAL Ventilation unit Document D2609 Valid from 24 02 2017 Updated 07 04 2020 Model Vallox 096 MC R Vallox 096 MC L Type 3721 1...

Page 2: ...l panel ordered separately Vallox ProControl panel ordered separately Vallox Capto PTC EC control hood Vallox X Line PTXP MC control hood or Vallox X Line PTXPA MC control hood or dered separately 6 1...

Page 3: ...is in the summer mode i e post heating is turned off and the heat recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature...

Page 4: ...the outdoor air is faulty Check the sensor and the wires replace as required 6 The supply air fan has stopped Check the wiring of the fan replace the fan as required 7 The extract air fan has stopped...

Page 5: ...unit and the best filtering results The filter replacement interval depends on the ambient dust concentration It is recommended that the filters be replaced every spring and autumn or at the very lea...

Page 6: ...from the bottom edge of the duct The extract air duct can now be removed by simultaneously turning and pushing it downwards figures 2 and 3 Remove the temperature sensor from the resistance support fi...

Page 7: ...ver figure 6 This will make the fan fall downwards Pull the fan out of the unit figure 10 Disconnect the quick connector of the fan cables F P 8 10 9 CONDENSING WATER In the heating season the extract...

Page 8: ...ct air TECHNICAL SPECIFICATIONS Nimike Vallox 096 MC R Vallox 096 MC L Product number 3474600 3474700 Air volumes Supply air Extract air 92 dm3 s 100 Pa 95 dm3 s 100 Pa Electrical connection 230 V 50...

Page 9: ...dB LWA dB A 57 61 65 68 71 74 76 78 79 79 52 56 64 66 71 74 76 79 80 80 34 39 44 47 51 54 56 59 60 60 33 39 45 48 52 55 58 61 63 63 Sound pressure level coming through the envelope of the unit in the...

Page 10: ...Vdc 1 Control signal S DIP switch 1 Post heating 2 Additional heating 3 Type of the unit 4 Extra Up Electric Electric Bypass Down VKL MLV Supply fan stop An external 0 10 V DC voltage supply can be co...

Page 11: ...GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL SITUATION OPEN A...

Page 12: ...5 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10 V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox ProControl 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11 2 V...

Page 13: ...10 mm higher than the final height 433 The minimum distance between the top of the unit and the finished ceiling surface is 30 mm The outer diameter of the duct is 12mm 162 12 21 20 60 2030 30 20 60...

Page 14: ...he mounting supplies delivered with the mounting plate Note The end of the thread bars must be 5mm or less below the fastening nut more detailed instructions are provided with the ceiling mounting pla...

Page 15: ...method requires that there is a 47mm space underneath the unit The elbow requires a 38mm space when installed 5 395 8 15 15 630 5 395 8 15 15 630 5 395 8 15 15 630 Attic floor penetration plate option...

Page 16: ...plate 3080700 4 Siphon Vallox Silent Klick 3292500 5 Coarse filter for supply air 978044 6 Fine filter for supply air 978220 7 HR cell 933260 8 Upper support for HR cell 3467200 9 Filter stand extract...

Reviews: