INSTALLATION SITE
Vallox 096 MC must be installed in a location where
the temperature remains above +10 °C. When the unit
is installed without a protective enclosure, the location
must be chosen so that its noise does not cause any
disturbance. Such locations include storage premises and
technical spaces.
5
380
Bottom edge
of the wall
mounting plate
165
Note that during mounting
the unit rises 10 mm higher
than the final height.
433
The minimum distance
between the top
of the unit and the
finished ceiling
surface is 30 mm.
The outer diameter of the duct is 12mm
162
12
21
20 60
2030 30
20
60
11
20
30
30
11
84
84
35 30
35
ø7 14 pc
550
30
25
25
30°
Wall mounting plate
Wall mounting
Mount the Vallox 096 MC on the wall with a mounting
plate, as shown in the adjacent figure. Make sure that the
unit is horizontally level after mounting.
Wall structure
The wall structure must be observed in the mounting.
Avoid mounting the unit on hollow, echoing intermediate
walls and on bedroom walls, or take measures to prevent
conduction of noise.