background image

BUS BODY ELECTRONICS

 

 

 

2.6  Errors 

 

2.6.1  Error detection mode 

2.6.1.1 Activation 

Press 

and 

 buttons at the same time for 2 seconds

 

  Mode is on. 

  Error code (F001) and occurrence count (1 here) will 

be displayed (Figure 14). 

2.6.1.2 Error detection 

  Scroll through the error codes with 

 or 

  Reset the counter with 

 (after resetting, the coun-

ter shower the value 1 if the error persists). 

2.6.1.3 Ending 

Press 

 and 

 buttons for 2 seconds 

  Normal operating display appears (Figure 15). 

 

 

 

Note 

If a system error occurs, the error symbol will appear on the 

display (Figure 13). 

 

Figure 13 - SC600 errors 

 

Figure 15 - SC600 normal operating 
display 

Figure 14 - SC600 Error detection mode

 

Summary of Contents for SC600 Australien

Page 1: ...Rev 21 11 2018 Id No DOK30605 BUS BODY ELECTRONICS SC600 AUSTRALIEN Operating instructions Busdriver...

Page 2: ...2 Use 6 2 1 Activation deactivation 6 2 1 1 Activation 6 2 1 2 Deactivation 6 2 2 Auto mode 6 2 2 1 Activation 6 2 2 2 Deactivation 7 2 3 Configuring the blowers manually 7 2 3 1 Activating the contro...

Page 3: ...SC600 Auto mode activated Cooling mode 6 Figure 8 SC600 Auto mode activated Heating mode 6 Figure 9 SC600 Auto mode deactivated 7 Figure 10 SC600 setting the blower level manually 7 Figure 11 SC600 r...

Page 4: ...This control panel allows the driver to control the roof top air conditioning system that has ven tilation cooling and heating functions for the roof Additionally this control panel can also be used t...

Page 5: ...isplay 1 Display 2 On off button 3 UP button 4 DOWN button 5 Function status light 6 Blower button 7 Fresh air recirculating air button 8 Auto button A Desired value display room temperature B Blower...

Page 6: ...unctions and infor mation summa rized under point 2 as well as Error mode The normal operat ing display includes all of the elements provided here in the example Error detection mode Mode to display a...

Page 7: ...corresponding status light and function symbol light up on the display Figure 6 Note Auto mode can be turned on only if the motor has been started Note If Auto mode is on the system automatically tur...

Page 8: ...3 2 Setting blower level The blower can be set in level increments of 0 blower speed 0 to 10 blower speed 100 Press button Blower level 1 Press button Blower level 1 Note When Auto mode is deactivate...

Page 9: ...tes the system turns off the manual recirculating air function The system then controls the fresh air valves automatically Pressing the button again within 10 minutes will de activate the manual recir...

Page 10: ...rror detection Scroll through the error codes with or Reset the counter with after resetting the coun ter shower the value 1 if the error persists 2 6 1 3 Ending Press and buttons for 2 seconds Normal...

Page 11: ...rness de fective F020 Room temperature sen sor Defective sensor Wiring harness de fective F021 Environmental tempera ture sensor Defective sensor Wiring harness de fective F022 Ice sensor Icing Temper...

Page 12: ...Valeo Thermal Commercial Vehicles Germany GmbH Postfach 1371 82198 Gilching Germany Tel 49 0 8105 7721 0 Fax 49 0 8105 7721 889 www valeo thermalbus com service valeobus valeo com...

Reviews: