Dedicated Outdoor Air Unit
25
Start-Up Checklist - Packaged Direct Expansion (PDX)
Compressor 1
Compressor 2
Compressor 3
Compressor 4
L1
Amps
Amps
Amps
Amps
L2
Amps
Amps
Amps
Amps
L3
Amps
Amps
Amps
Amps
Crankcase Heater
Not present on inverter compressor
Amps
Amps
Amps
Amps
Superheat
(Models VX/VXE-112, -212, and -311)
Should be between 8º and 12ºF
Deg. F
Deg. F
Deg. F
Deg. F
Subcooling
(Models VX/VXE-112, -212, and -311)
Should be between 8º and 12ºF
Deg. F
Deg. F
Deg. F
Deg. F
Superheat
(Models VX/VXE-352)
Should be between 10º and 20ºF (0% reheat)
or should be between 10º and 30ºF (100%
reheat)
Deg. F
Deg. F
Deg. F
Deg. F
Subcooling
(Models VX/VXE-352)
Should be between 10º and 15ºF (0% reheat)
or should be between 2º and 10ºF (100%
reheat)
Deg. F
Deg. F
Deg. F
Deg. F
Discharge Pressure
Should be between 300 and 500 PSIG
PSIG
PSIG
PSIG
PSIG
Suction Line Pressure
Should be between 100 and 135 PSIG
PSIG
PSIG
PSIG
PSIG
Liquid Line Temp.
Deg. F
Deg. F
Deg. F
Deg. F
Suction Line Temp.
Deg. F
Deg. F
Deg. F
Deg. F
Moisture Indicating Sight Glass
Liquid Visible
Yes / No
Yes / No
Yes / No
Yes / No
Color of Center Dot
Purple / Pink
Purple / Pink
Purple / Pink
Purple / Pink
Hot Gas Bypass Operational
Yes / No / NA
NA
NA
NA
Start-Up Checklist - Packaged Direct Expansion (DX)
Summary of Contents for VX Series
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......