valent VX Series Installation, Operation And Maintenance Manual Download Page 15

Dedicated Outdoor Air Unit

15

Phase Monitor

The unit control circuitry includes a phase monitor that 
constantly checks for phase reversal, phase imbalance, 
loss of phase or a power brownout. When it detects a 
fault, it cuts off the 24 VAC that goes to the low voltage 
terminal strip, thereby shutting off all motors.

Variable Frequency Drive (VFD)

If a VFD was provided and installed at the factory, it has 
been pre-set to control the speed of the blower motor 
for optimum performance. The motor speed needs to be 
verified during test and balance of the unit. 
If the system was configured for Constant Air Volume 
(CAV), the VFD will operate in an ON/OFF fashion 
and the speed of the motor will not change. If the 
system was configured for Variable Air Volume (VAV), 
the microprocessor will constantly monitor operating 
conditions and provide a signal to the VFD, changing 
the VFD output as needed.
The VFD may alternatively be connected to an external 
signal such as provided by a BMS and be operated by a 
2-10 VDC or a 4-20 mA input.

Supply Fan VFD Sequence

Optional Room CO2 Sensor:  

The microprocessor will 

modulate the supply fan based on a comparison of the 
CO2 set point to the actual CO2 levels reported from 

the sensor. Mechanical high static protection cutoffs 
must be installed by others to protect the system and 
equipment from over-pressurization.

Optional Duct Static Pressure Sensor:  

The 

microprocessor will modulate the supply fan based 
on a comparison of the duct static pressure set point 
to the actual duct static pressure level reported from 
the sensor. Mechanical high static protection cutoffs 
must be installed by others to protect the system and 
equipment from over-pressurization. The manufacturer 
does not assume responsibility for this.

Optional Building Static Pressure Sensor:  

The 

supply fan is modulated based upon the signal from a 
building static pressure sensor. The microprocessor will 
modulate the supply fan based on a comparison of the 
building static pressure set point to the actual building 
static pressure level reported from the sensor.

Optional Single Zone VAV:  

The microprocessor will 

use a space mounted temp sensor to vary heating and 
cooling capacity and the airflow delivered by the fan to 
maintain room-air temp at a desired set point.

Optional 0-10 VDC by others to VFD:  

Supply fan is 

modulated by a  0-10 VDC, field-provided by others.

Component Operation

Exhaust Fan VFD Sequence

Optional Building Static Pressure Sensor:  

The 

exhaust fan is modulated based upon the signal from 
a building static pressure sensor. The microprocessor 
will modulate the exhaust fan based upon a comparison 
of the building static pressure level reported from the 
sensor.

Optional Outdoor Air Damper Tracking:  

The 

microprocessor will proportionally modulate the exhaust 
fan based upon the outdoor air damper position.

Optional Supply Tracking:

  The microprocessor will 

proportionally modulate the exhaust fan based upon the 
supply fan.

Optional 0-10 VDC by Others to VFD:

  The supply fan 

is modulated by a 0-10 VDC provided by others in the 
field.

Outdoor Air and Recirculated (Recirc) Air 

Damper Sequence

Optional Room CO2 Sensor:  

The microprocessor 

will proportionally modulate the OA/RA dampers based 
upon a comparison of the CO2 set point to the actual 

CO2 level reported from the sensor. As the CO2 level 

rises, the controller will proportionally modulate the 
outdoor air damper open, between the minimum and 
maximum OA position.

Optional Building Pressure:  

The OA/RA dampers 

will modulate based upon the signal from a building 
static pressure sensor. The controller will modulate 
the dampers, between the minimum and maximum OA 
positions, based upon a comparison of the building 
static pressure set point to the actual building static 
pressure level reported from the sensor.

Exhaust Fan Only Power

The exhaust fan will have a dedicated power circuit 
where in the case of a power outage, the exhaust fan 
will still run. A phase monitor will detect an outage or 
power loss and open the contact, disconnecting all 
power to the unit and controller. An external signal will 
need to be sent to a relay to power the exhaust fan, 
enabling  the fan to run at a maximum speed. This 
sequence is NOT to be used for high temperature 
exhaust applications.

Vapor Tight Lights

Vapor tight lights provide light to each of the 
compartments in the energy recovery unit. The lights 
are wired to a junction box mounted on the outside of 
the unit. The switch to turn the lights on is located in 
the unit control center. The switch requires a separate 
power source to allow for power to the lights when the 
unit main disconnect is off for servicing.

Optional Component Operation

Summary of Contents for VX Series

Page 1: ...ause bodily harm CAUTION When servicing the unit the internal components may be hot enough to cause pain or injury Allow time for cooling before servicing Only qualified personnel should install and m...

Page 2: ...Piping Installation 12 Electrical Information 13 Control Center Components 14 Component Operation 15 Optional Component Operation 15 18 Factory Installed Refrigeration System 19 21 Start Up Unit 22 2...

Page 3: ...f dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose to permit air circulation and to allow for...

Page 4: ...ilable on VX VXE 311 and 352 Packaged DX and ASHP units are shipped fully charged with refrigerant and are ready for operation upon arrival Heating There are three different optional heat sources that...

Page 5: ...ng 311 uses furnace model PVF 200 600 or model HMA 700 800 Housing 352 use furnace model HMA 600 1200 Packaged DX System Any unit may be ordered with a packaged DX system Housing size 112 will include...

Page 6: ...224 22 27 30 8 300 VXE 352 30 70 99 5 96 263 307 47 NA 10 450 Bottom or Side Side All dimensions are shown in inches Weight is shown in pounds and includes largest supply and exhaust fans PDX with re...

Page 7: ...Unit Size ACS Access Side CC Control Cabinet End OAI Outdoor Air Intake NA from Unit NA from Condensing Section NA from Piping Vestibule not shown Other Indoor Mounted with IG Furnace Outdoor Mounted...

Page 8: ...with a defrost cycle to remove ice from the outdoor coil During defrost cycles melted water may drip from the bottom of the refrigeration section under the outdoor coil In cold climates proper draina...

Page 9: ...openings Guide unit while lowering to align with duct openings Roof curbs fit inside the unit base Make sure the unit is properly seated on the curb and level 5 Install Vestibule If unit was ordered w...

Page 10: ...an L configuration and the area directly beneath the heat source must not have any openings such as louvers or grates No louvers or grates Installation Typical Unit Installed on Rails Supplied by Oth...

Page 11: ...rvice and gas supply be brought into the cabinet through the end wall as shown below There are three penetrations into the cabinet that are required one for high voltage supply wiring one for low volt...

Page 12: ...epted industry standards Pipework should be supported independently of the coils Undue stress should not be applied at the connection to coil headers 2 The condensate drain pipe should be sized adequa...

Page 13: ...isconnect and must be compatible with the ratings on the nameplate supply power voltage phase and amperage Consult ANSI NFPA 70 and CSA C22 1 for proper conductor sizing Provide the Opening s for the...

Page 14: ...Outdoor airflow monitor 17 Exhaust airflow monitor 18 Digital scroll controller Optional Indirect Gas Fired Furnace Note In some models two furnaces are installed to provide greater output When two fu...

Page 15: ...ain room air temp at a desired set point Optional 0 10 VDC by others to VFD Supply fan is modulated by a 0 10 VDC field provided by others Component Operation Exhaust Fan VFD Sequence Optional Buildin...

Page 16: ...ling mode the following conditions must be true 1 Supply air temperature above minimum low supply temperature limit 35 F 2 Outside air temperature above the cooling ambient lockout 55 F adj To operate...

Page 17: ...en the system undergoes test and balance Hot Gas Reheat Valve Units equipped with a reheat coil use a three way valve with actuator to control the supply air discharge temperature of the unit during d...

Page 18: ...l be fully programmed at the factory Optional Component Operation Rotation Sensor The rotation sensor monitors energy wheel rotation If the wheel should stop rotating the sensor will close a set of co...

Page 19: ...ble and is located on the side of the evaporator coil and can be accessed through the coil access panel 13 Evaporative Coil 14 Low Limit Pressure Switch The switch is installed on the suction line and...

Page 20: ...Source Heat Pump with Three Way Hot Gas Reheat 4WV Outdoor Coil Indoor Coil Outdoor Airflow Hot Gas Reheat Coil Supply Airflow Compressor PT HRV LPS SG SG EXV FDS HPS SV HCV ACC 4WV Outdoor Coil Indoo...

Page 21: ...rsing valve to reverse the direction of refrigerant flow switching the unit between heating and cooling mode 12 Electronic Expansion Valve EXV or Thermostatic Expansion Valve TXV An expansion valve is...

Page 22: ...or Allow 5 minutes between on cycles to prevent compressor damage DX system is charged with refrigerant Start up must be performed by EPA Certified Technician Start Up Unit Every installation requires...

Page 23: ...ital scroll compressor The variable speed compressor uses internal stator heating Each compressor needs power supplied to it 24 hours prior to start up If start up is scheduled in 24 hours unlock the...

Page 24: ...Energy Wheel Motor if equipped L1 Amps L2 Amps L3 Amps Condensing Fans PDX only Condensing Fan 1 L1 Amps L2 Amps L3 Amps Condensing Fan 2 L1 Amps L2 Amps L3 Amps Condensing Fan 3 L1 Amps L2 Amps L3 Am...

Page 25: ...ween 10 and 20 F 0 reheat or should be between 10 and 30 F 100 reheat Deg F Deg F Deg F Deg F Subcooling Models VX VXE 352 Should be between 10 and 15 F 0 reheat or should be between 2 and 10 F 100 re...

Page 26: ...n Line Temp Deg F Deg F Moisture Indicating Sight Glass Liquid Visible Yes No Yes No Color of Center Dot Purple Pink Purple Pink Heating Superheat Should be between 10 and 20 F Deg F Deg F Subcooling...

Page 27: ...ntrol center door Vibration Excessive vibration may be experienced during initial start up Left unchecked excessive vibration can cause a multitude of problems including structural and or component fa...

Page 28: ...ess ENTER 7 Set number of flows and press ENTER 8 Set flow and press ENTER 9 Set flow to actual CFM measured by Test and Balance and press ENTER 10 Wait for calibration before cycling power 11 Proceed...

Page 29: ...re that you do not have power at the alert signal leads The unit is now ready for operation Setscrew on front of switch must be manually adjusted after the system is in operation Negative pressure con...

Page 30: ...the factory but are field adjustable The VFD will be fully programmed at the factory Optional Energy Wheel Start Up If selected the energy wheel is installed in the unit s airstream with one half of...

Page 31: ...e when a clip is open the clip will jam against the bearing support bar and could cause damage Cleaning Maintenance or cleaning of the wheel segments should be done with the segments removed from the...

Page 32: ...dition is corrected It is located in the main control center Variable Frequency Drive VFD Variable frequency drives have a display screen that will show an alarm condition If a fault such as a voltage...

Page 33: ...rted windings in motor Replace motor Low airflow cfm Unit damper not fully open Adjust damper linkage or replace damper motor System static pressure too high Improve ductwork to eliminate losses using...

Page 34: ...and repair Replace fuse after correcting problem Low line voltage Check line voltage If more than 10 from compressor marking correcting is necessary Compressor motor protector open Motor thermal prote...

Page 35: ...for two hours Recheck for open circuit Improper refrigerant charge Check subcooling Improperly wired Review wiring schematics Loose wiring Check all connections Defective start relay Replace relay Mot...

Page 36: ...sible air recirculating Clean coil Condenser fan motor defective Check condenser fan motor Too much refrigerant Check subcooling Remove excess refrigerant Non condensable in system Remove non condensa...

Page 37: ...ings Refrigerant flood back Check thermal expansion valve setting Check for refrigerant overcharge Check crankcase heater operation Reheat flush cycle inadequate Contact factory Not enough capacity or...

Page 38: ...ntenance session and observations and then establish a maintenance schedule that is appropriate for the installation The following is provided as a guideline Maintenance Frequency Monthly 1 External F...

Page 39: ...ces only Removing dust and grease buildup on the motor housing assists proper cooling Never wash down the motor with high pressure spray Greasing of motors is only intended when fittings are provided...

Page 40: ...0x25x2 2 20x25x2 4 20x20 VXE 212 4 25x25x2 4 16x25x2 4 16x25x2 8 16x25 VXE 311 6 20x25x2 7 16x20x2 7 16x20x2 12 16x20 VXE 311 6 25x25x2 8 20x20x2 20x24x2 8 20x20x2 20x24x2 12 16x20 VXE 352 30 40 tons...

Page 41: ...212 300 14 8 23 3 38 1 44 1 6 6 6 400 6 6 6 500 14 9 23 6 25 2 57 1 6 6 6 B A C D 500MBH 300 400MBH A B C D 200 300MBH 100 150MBH C A B D C A B D COMBUSTION AIR INLET EXHAUST OUTLET IG FURNACE ACCESS...

Page 42: ...ng Location Model Furnace Size MBH A B C D E F G H I J Inlet Dimensions Outlet Dimensions Length Height Edge Thickness Length Height VX VXE 352 600 6 13 8 17 2 20 5 50 NA NA NA NA NA 21 5 6 1 6 5 5 5...

Page 43: ...X 112 15I 3775 VX 112 15D 3775 VX 112 15S 3775 VX 112 15A 4300 VX 212 15I 4100 VX 212 15D 4100 VX 212 15S 4100 VX 212 15A 4800 Model Airflow SCFM VX 212 17 5I 4650 VX 212 17 5D 4650 VX 212 17 5S 4650...

Page 44: ...8th Avenue North Minneapolis MN 55411 Main 612 877 4800 MORE INFORMATION UNIT SCHEMATICS For configuration and connection questions see the schematics that shipped with your unit They can typically be...

Page 45: ...ause bodily harm CAUTION When servicing the unit the internal components may be hot enough to cause pain or injury Allow time for cooling before servicing Only qualified personnel should install and m...

Page 46: ...ntenance session and observations and then establish a maintenance schedule that is appropriate for the installation The following is provided as a guideline Maintenance Frequency Monthly 1 External F...

Page 47: ...ces only Removing dust and grease buildup on the motor housing assists proper cooling Never wash down the motor with high pressure spray Greasing of motors is only intended when fittings are provided...

Page 48: ...0x25x2 2 20x25x2 4 20x20 VXE 212 4 25x25x2 4 16x25x2 4 16x25x2 8 16x25 VXE 311 6 20x25x2 7 16x20x2 7 16x20x2 12 16x20 VXE 311 6 25x25x2 8 20x20x2 20x24x2 8 20x20x2 20x24x2 12 16x20 VXE 352 30 40 tons...

Page 49: ...including proper refrigerant charge and repair of minor refrigerant leaks outside the coil At the completion of start up an approved start up record must be submitted to the Unison service department...

Page 50: ...te of shipment from the Unison factory whichever occurs first The ship date for the units noted above is 5 4 2020 Please refer to the Unison Comfort Technologies terms and conditions of sales for addi...

Page 51: ......

Page 52: ......

Page 53: ......

Page 54: ......

Page 55: ......

Page 56: ......

Page 57: ......

Page 58: ......

Page 59: ......

Page 60: ......

Page 61: ......

Page 62: ......

Page 63: ......

Page 64: ......

Page 65: ......

Page 66: ......

Page 67: ......

Page 68: ......

Page 69: ......

Page 70: ......

Page 71: ......

Page 72: ......

Reviews: