VRC Series IOM
6
IOM-M2-0316
Technical Support: (800) 789-8550
Part Number 478603
Installation
Receiving and Inspection
Visually inspect the unit before unloading and note
any damage in writing on the delivery receipt. If the
unit is damaged during shipping, the customer should
immediately file a claim with the shipping company
and notify the manufacturer. Photograph the damage
if possible.
Verify that all pieces listed on the bill of lading have
been received.
Storage
Any unit stored outdoors prior to installation should
be covered. Do not store other equipment on top of or
inside the unit.
Temporary Use
This equipment must not be used as:
Temporary heating or cooling
Construction heating
The units should not be operated until construction is
complete and the units have properly undergone the
pre-startup and startup routines.
Sound Insulation
If the ventilator (indoor) unit is to be installed above
or adjacent to a sound-critical area such as an office,
precautions should be taken to sound insulate
mechanical room walls, floor, or ceiling to minimize
unit noise transmission.
Pad Installation
▪
Check to make sure the pad is level.
▪
Lift unit into place per the
Lifting Procedure
on
page 4.
▪
Secure the unit to the pad in accordance with all
applicable building codes.
Refer to the following
Minimum Pad Dimensions
.
Equipment Support Installation
▪
Ensure that equipment supports are level. Space
supports as shown in the drawing below.
▪
Lift unit into place per the
Lifting Procedure
on
page 4.
▪
Place unit on supports such that one support is
under each end of the unit (see drawing below).
▪
Secure the unit to the supports in accordance with
all applicable building codes.
Refer to the following
Equipment Support
Dimensions
.