Page 32
Installation Manual - SRF40
ENGLISH
VENTING
4.4.5 Horizontal Installation
ONE 90° ELBOW
A
TO BOTTOM
OF UNIT
B
INSTALLED
VERTICALLY
1’
MINIMUM
Example Vent Runs
Initial Pipe
Length
A (Vertical)
B (Horizontal)
Maximum
(Dimensions In Inches)
12
60
24
24
72
72
36
84
108 (9 ft)
48
96
144 (12 ft)
Note:
Pipe straps must be used every 2 feet to secure
venting. Minimum rise of the fireplace is 1 foot.
TWO 45° ELBOWS
Note:
Subtract 1-1/2 feet from the total horizontal measurement for each 45° elbow installed horizontally.
B
A
Example Vent Runs
Initial Pipe
Length
A (Vertical)
B (Horizontal)
Maximum
(In Inches)
(In Feet)
12
6
6
24
7
9
36
8
12
48
9
15
Minimum rise of the fireplace is 1 foot.
TWO 90° ELBOWS
Note:
Subtract 3 feet from the total horizontal measurement for each 90° elbow installed horizontally.
Example Vent Runs
Initial Pipe
Length
A (Vertical)
B (Horizontal)
Maximum
(Dimensions In Inches)
12
60
Not Allowed
24
72
36
36
84
72 (6 ft)
48
96
108 (9 ft)
Minimum rise of the fireplace is 1 foot.