Installation Manual - L48
ENGLISH
VENTING
The vertical termination cap
for this fireplace
must not be any closer than 24 in. to combustible
materials.
If two vertical terminations are run near each
other
, they may be placed a minimum of 12 inches
between them if they are at the same height. If
two vent terminations are not at the same height,
they must be positioned at least 24 inches apart
to minimize draft issues between them.
12”
MINIMUM
4.7.1 Approuved Venting Component
The following vent systems are acceptable for use with the L48 fireplace:
• Simpson Duravent® GS 5 in - 8 in
• American Metal Products 5 in - 8 in
• Selkirk Direct-Temp®
5 in - 8 in
• Security Secure Vent® 5 in - 8 in
• Excel DV Venting
5 in - 8 in
• Olympia Ventis
5 in - 8 in
• BDM
5 in - 8 in
• Metal Fab
5 in - 8 in
40’
(12.19M)
MAX
24” MINIMUM
CLEARANCE TO
COMBUSTIBLES
NATURAL OR
MAN MADE
96” (2.44M)
MAX
(2.44M)
MAX
45°
45°
96”