VL-9998RM, VL-9998WM  

SUPERVISED IDF  

 

Introduction 

These instructions contain the specifications 
and guidelines necessary to install, operate, 
and maintain the VL-9998RM Rack Mount and 
VL-9998WM Wall Mount Supervised IDF. 
 
The VL-9998RM and VL-9998WM provide 
audio, 24VDC and wire monitoring for up to 12 
supervised self amplified speaker runs in a 
single zone configuration, or may be 
configured for 2 paging zones with 6 speaker 
runs in each zone.  Up to (6) 1 watt interior 
speakers may be connected to each output or 
(1) 5 Watt Paging horn.  

Consult Valcom 

Services LLC for other configurations.

  

 
The unit provides both audible and visual 
indication of wire faults

 

 

Features 

 

Red Alarm Led 

 

Power Indicators (Green) 

 

Pushbutton Switch (Fault Silence) 

 

Individual Speaker Line Status Indicators 
(Red Led’s) 

 

Bypass Selection for Each Output 

 

Buzzer for Audible Alarm 

 

Two Audio Input 110 Terminal 
Connections 

 

Programmable Fault Contact Connection 

 

EOL (4.7k Ohm) Fault Connection 

 

Speaker Cable Connection: 8 Position 110 
Terminals  

 

Alarm Output Connection

 

 

Power Requirements 

 

Operating Voltage 24 

– 26 VDC 

 

Current 100mA 

 

System Supervision 

Speaker Audio Output 

– DC loop terminated 

with a V-9999 EOL unit. 
 
All system faults are indicated by both an 
audible and visual alarm.  The audible alarm 
may be silenced however the visual indicator 
will continue to illuminate until the fault is  

 
 
 
repaired.  The fault will 

“auto reset” after the 

circuit is repaired.  
  
If unit is configured for 2 page zones, it 
appears as a single fault to the monitoring 
system.  

 

User Controls 

 

Push button silence switch 

– Silences 

local audible alarm only 

 

Zone supervision by-pass jumper - 
(Removes supervision from unused 
outputs) 

 

Program Jumpers 

– (Allows the unit to 

provide supervision for 2 page zones 

– 6 

speaker circuits each).  Allows the unit to 
have separate power for each group of 6 
speaker circuits and allows the fault 
contact to be N.O. (Open during Fault) or 
N.C. (Closed during Fault).  

 

Indicators 

 

Power “ON” Green Led 

 

Red Alarm Led for each output 

 

Visual system main fault 

 

Audible system fault with silence button  

 

Inputs 

 

One audio input for each zone of 6 
speaker line connections. 

 

Outputs 

 

12 speaker line outputs divided into 2 
zones six speaker lines each. 

 

External alarm output (contact closure) 

 

System Operation 

The supervision module continuously monitors 
the speaker runs for both opens or shorts and 
provides both audible and visual indication of 
wire faults.

 

In the event of a speaker run wire 

fault, the VL-9998 provides a red LED 
indication identifying which speaker run has 
the fault and sounds a local buzzer on the 
panel for an audible alarm.  A contact closure 