CAUTION!!!!

 

Never connect two actuators to the same terminal block

 
No external controls are provided with standard Failsafe units. All manual switch/controls are to 
be provided by the customer, and should be connected according to the electrical drawing, or 
drawings provided with the Failsafe unit and the switch/control manufacturer.  Wiring must 
comply with all Federal, State, and local codes. 
 
If your Fail-safe unit is controlling a modulating actuator (

4/20 ma signal

 ), regardless of the 

source of the signal,  the Failsafe unit will cut the (

4/20 ma signal)

 to the actuator and drive it 

down to zero (

0 ma ). 

 This will force the actuator to move to its failsafe position. For this type 

of operation the signal wires should be connected as follows: 
 
1. - Connect the negative

 (-)

 wire from the 4 /20 ma source to the terminal labeled signal (-) at 

the actuator. 
 
2. - Connect the positive 

(+)

 wire from the 4 / 20 ma source to one of the terminals labeled 

MOD

 

in the Failsafe unit. 
 
3. - Connect the other terminal labeled 

MOD 

at the Failsafe unit, to the terminal labeled signal 

(+)

 in the actuator. 

 
4. - Connect the normally open Limit Switch wires from the Actuator to the terminals labeled 

ALS

 in the Failsafe unit 

 
5. - Connect the motor from the Actuator to the Failsafe according to the drawings supplied with 
the unit. 
 
6. - Connect Power to the unit, make sure you connect a solid ground to the Failsafe 
 
7. - Install the Fuses; (they were shipped separately for security reasons.) 
 
 

 
 

WARNING ! 

 

 
Valcom does not recommend the use of any of its Failsafe units in life support systems or in 
any life threatening applications where a malfunction or failure of the unit could cause 
failure of these applications.  
 
 

 
 
 

Summary of Contents for 1620ES-24VDC Series

Page 1: ...Valcom Failsafe Unit 1620ES 24VDC SERIES Operation and Maintenance Manual...

Page 2: ...e Page 1 Introduction 2 Unpacking the Failsafe unit 3 Installation 3 1 Auto Timed UPS Shut Down 4 Failsafe Operation 5 Maintenance 5 1 Testing the Batteries 5 2 UPS RESET 6 Electrical Drawings 7 Speci...

Page 3: ...tached to the inside door and an extra set is supplied for your files Your Fail safe unit features sophisticated electronic circuitry It provides high peak power output to start and run devices requir...

Page 4: ...th these terminals during Failsafe operation or during service or installation You must insulate these terminals to help protect against accidental short circuits Failure to properly ground the Failsa...

Page 5: ...he controller for the system to shut down automatically after power failure TIMED MODE should be used only when the valve actuator does not have an available limit switch To enable this option jumpers...

Page 6: ...d as follows 1 Connect the negative wire from the 4 20 ma source to the terminal labeled signal at the actuator 2 Connect the positive wire from the 4 20 ma source to one of the terminals labeled MOD...

Page 7: ...resume normal operation If an OPEN CLOSE switch has been interfaced between the Failsafe unit and the actuator ensure that the actuator will go to the failsafe mode open or close regardless of the po...

Page 8: ...es are an indication of a fault in the system or its connections Such as short circuits overloads etc Locate the source of the problem before replacing the fuse The Failsafe unit operates at high effi...

Page 9: ...orm a test with a battery load tester 5 2 UPS RESET You may connect a momentary switch to the UPS RESET TB3 terminal block this will restore additional time of emergency power to the valve This featur...

Reviews: