panel to allow room for wires to clear all internal components. 

Do not make connections 

through the back of the control box

. All connections and conduit hubs must be of the type 

which will maintain the correct NEMA rating of your unit. 
 
All connections are to be made directly to the terminal block located inside the Failsafe unit; 
these terminals are clearly marked and assigned on the electrical drawings attached to the door. 
 
Make all the connections between the actuators and the Failsafe unit. When connecting the 

limit 

switches

 be sure that you have selected a set of contacts that

 

will 

close

 when the actuator has 

reached a 

FULLY OPENED 

or 

FULLY CLOSED 

position after power failure. Failure to 

select the correct set of contacts will prevent the Failsafe unit from automatically disconnecting 
after the actuators have reached the failsafe position.  
 

 
3.1. – AUTO / TIMED UPS shut down  
 

The 1620ES-24VDC series includes an option that allows the system to 
be shut down in 

AUTO

 or 

TIMED

 mode. 

 

AUTO

 

MODE

 requires that a Limit Switch from the valve actuator be 

connected to the controller for the system to shut down automatically 
after power failure. 
 

TIMED

 

MODE

 should be used only when the valve actuator does not 

have an available limit switch. 
 
To enable this option, jumpers 

J1

 and 

J2

 must be moved from pins 

1-2

 

to pins 

2-3

. Once enabled, the time available for a shut down after a 

power failure is selected with the potentiometer 

P3

, the minimum time 

is factory set at 4.5 minutes (P3 set fully to the left) and the maximum 
possible time to select is of 12.5 minutes (P3 set fully to the right). 
Longer times are available and should be requested when ordering.  
 
Regardless of the mode selected, this controller has an 

LED

 above 

P3

 that will be ON when the 

failsafe has been shut down after a power failure, and it will remain ON until normal power is 
restored. 
 
The battery included with this Failsafe unit was sized to operate a specific system for a specific 
amount of time. If it is not disconnected from the valve it will fully discharge the battery after 
activation. 
 
Ensure that all the electrical connections are made according to the drawings and schematics 
provided by the actuator manufacturer.  If more than one actuator is to be controlled by the 
Failsafe, each one should be connected to the assigned terminal block inside the Failsafe unit.  
 

 

Summary of Contents for 1620ES-24VDC Series

Page 1: ...Valcom Failsafe Unit 1620ES 24VDC SERIES Operation and Maintenance Manual...

Page 2: ...e Page 1 Introduction 2 Unpacking the Failsafe unit 3 Installation 3 1 Auto Timed UPS Shut Down 4 Failsafe Operation 5 Maintenance 5 1 Testing the Batteries 5 2 UPS RESET 6 Electrical Drawings 7 Speci...

Page 3: ...tached to the inside door and an extra set is supplied for your files Your Fail safe unit features sophisticated electronic circuitry It provides high peak power output to start and run devices requir...

Page 4: ...th these terminals during Failsafe operation or during service or installation You must insulate these terminals to help protect against accidental short circuits Failure to properly ground the Failsa...

Page 5: ...he controller for the system to shut down automatically after power failure TIMED MODE should be used only when the valve actuator does not have an available limit switch To enable this option jumpers...

Page 6: ...d as follows 1 Connect the negative wire from the 4 20 ma source to the terminal labeled signal at the actuator 2 Connect the positive wire from the 4 20 ma source to one of the terminals labeled MOD...

Page 7: ...resume normal operation If an OPEN CLOSE switch has been interfaced between the Failsafe unit and the actuator ensure that the actuator will go to the failsafe mode open or close regardless of the po...

Page 8: ...es are an indication of a fault in the system or its connections Such as short circuits overloads etc Locate the source of the problem before replacing the fuse The Failsafe unit operates at high effi...

Page 9: ...orm a test with a battery load tester 5 2 UPS RESET You may connect a momentary switch to the UPS RESET TB3 terminal block this will restore additional time of emergency power to the valve This featur...

Reviews: