Quick Guide ___________________________________________________________________ HMW80 

 

© Vaisala 2011. All rights reserved. ______________________________________________________ 2 

 

WIRING 

HMW82 

-T

4...20 mA

(-5 ... +55 ºC)

-RH

4...20 mA

(0 ... 100% RH)

+T

+RH

Power supply
10 ... 28 VDC
R

L

 = 0 ... 500 

Power supply
10 ... 28 VDC
R

L

 = 0 ... 500 

mA

mA

 

You must connect the RH channel 
of the HMW82

, even if you only 

want to measure temperature. 
 
Connecting the T channel is optional.

TMW82 

-T

4...20 mA

(-5 ... +55 ºC)

+T

Power supply
10 ... 28 VDC
R

L

 = 0 ... 500 

mA

 

Leave the two terminals on the left 
unconnected. 

HMW83 

-T

0...10 V

(0...100 %RH)

-VS

+T

+VS

Power supply
15 ... 35 VDC
or 24 VAC ±20%
R

L

 = 10 k

 min.

-RH +RH

0...10 V
(-5...+55 ºC)

V

V

 

-T

-VS

+T

+VS

Power supply
15 ... 35 VDC
or 24 VAC ±20%
R

L

= 10 k

min.

-RH +RH

V

V

0...10 V

0...10 V

 

Recommended wiring for long cables. 

3-wire connection with -VS as common 
ground. Not recommended if cable resistance is 
more than 2.5 

TMW83 

-T

0...10 V

(-5 ... +55 ºC)

-VS

+T

+VS

V

Power supply
15 ... 35 VDC
or 24 VAC ±20%
R

L

 = 10 k

 min.

 

-T

-VS

+T

+VS

V

Power supply
15 ... 35 VDC
or 24 VAC ±20%
R

L

 = 10 k

 min.

0...10 V

 

Recommended wiring for long cables. 

3-wire connection with -VS as common 
ground. Not recommended if cable resistance is 
more than 2.5 

 