Operating Manual

1996-04-12

1

HUMIDITY TRANSMITTER HMD60U

HUMIDITY AND TEMPERATURE TRANSMITTER HMD60Y

MOUNTING

Ø 12

(0.47)

250  (9.84)

62 (2.44)

100  (3.94)

1

00  (3.

94)

M

ount

ing 

hole

 82 (3.

2

3)

>

>

>

Mounting hole 82 (3.23)>>>

The HMD60U/Y humidity and
temperature transmitters are two-wire
transmitters. They are duct mounted, and
the electronics can be disconnected
without dismantling the installation.

Mount the transmitter with two screws.
Place the drilling template on the duct
surface and drill the holes as indicated.
Remember to drill an additional hole for
calibration purposes. The calibration can
be conveniently performed on site with
the HMI41 indicator equipped with an
appropriate probe and optional
calibration cable.

Figure 1  Dimensions of the HMD60U/Y

GROUNDING

(If the cable diameter is less

than 7mm, use a shrinking
tube or an adhesive tape)

cable

braid

flexible wires 0.5 mm²                

(AWG 20), stranded wires

recommended 

D = Ø 7...10mm

3

brass
disks

25

rubber

ring

nut

brass disks

140

165

shielding tube

braid

Figure 2  Signal cable grounding  with
bushing 18941HM

Open the lid and mount the cable
bushing set 18941HM. Do the grounding
according to Figure 2. W

hen connecting

the signal cable to the transmitter housing,
fold the cable braid between the brass disk
in order to achieve the best EMC per-
formance. Do not leave the bare shield of
the connected wires so that it can
shortcircuit the electronics!

Summary of Contents for Humicap HMD60U

Page 1: ...n can be conveniently performed on site with the HMI41 indicator equipped with an appropriate probe and optional calibration cable Figure 1 Dimensions of the HMD60U Y GROUNDING If the cable diameter i...

Page 2: ...ET T TEST 1 2 3 4 5 mA TEST RH mA mA mA or or Figure 3 Electrical connections Signal cables are connected to a removeable 5 pole screw connector Make the connections according to Figure 3 above RH tes...

Page 3: ...racy is recommended to be checked at least once a year the interval depends on the operating conditions and the required accuracy of the measurement The transmitter calibration can be conveniently che...

Page 4: ...ing cast aluminium Cable lead through bushing for 7 10 mm PG9 cable housing IP65 NEMA 4 part no 18941HM or armoured cable glands part no 10528HM Sensor protection standard membrane filter part no 1703...

Page 5: ...RH T X3 X4 UP wet dry HUMICAP sensor sensor Figure 2 Electrical connections Signal cables are connected to a removeable 5 pole screw connector Make the connections according to Figure 2 110 4 33 85 3...

Page 6: ...ge temperature range 40 80 C Long term humidity range for electronics 0 85 RH Housing cover ABS plastic base plate PA Connections Screw terminals 0 5 1 5 mm2 Electromagnetic compatibility The emission...

Page 7: ...rformed on site with the HMI41 indicator equipped with an appropriate probe and optional calibration cable GROUNDING If the cable diameter is less than 7mm use a shrinking tube or an adhesive tape cab...

Page 8: ...SUPPLY HMD70U Y transmitter Controller VAC VAC Us GND signal RH T GND Us RH T signal HMD70U Y transmitter Figure 4 The recommended AC connection HMD70U Y transmitter HMD70U Y transmitter Controller s...

Page 9: ...he accuracy is recommended to be checked at least once a year the interval depends on the operating conditions and the required accuracy of the measurement When checking the transmitter calibration us...

Page 10: ...s less than 0 5 RH without recalibration Operating temperature range electronics 5 55 C sensor head 40 80 C Storage temperature range 40 80 C Housing sensor head stainless steel electronics housing ca...

Page 11: ...te the UP sign which shows the correct mounting position Be careful not to damage the HUMICAP 180 sensor ELECTRICAL CONNECTIONS AND CALIBRATION POTENTIOMETERS RHout Tout Us GND T RH 0 1V 0 5V RH T T R...

Page 12: ...s an increased risk of a short circuit To avoid this use a separate floating supply for each transmitter see Figure 3 However if several transmitters have to share one transformer the phase must alway...

Page 13: ...rs connections An output change causes an error which is less than 0 5 RH without recalibration Operating temperature range 5 55 C Storage temperature range 40 80 C Long term humidity range for electr...

Reviews: