2. Log in to the web interface as an administrator user.
3. Select
Inputs and outputs > Relays
.
4. Select the relay you want to configure:
Relay 1
or
Relay 2
.
5. Configure the relay settings:
a. In
Relay off/on
, set the relay off to edit settings.
b. In
Source
, select the source for the measurement parameter that controls the relay.
c. In
Parameter
, select the measurement parameter that controls the relay.
d. In
Activation
, select whether the relay activates above or below the activation/
deactivation limit.
e. In
Limit
, define the limit which the measured parameter value must reach for the relay
to activate/deactivate.
f. In
Hysteresis
, define a buffer value for relay deactivation. With hysteresis, an
activated relay switches off only when the measured value crosses the relay
activation/deactivation limit and the additional buffer value.
g. In
Relay off/on
, set the relay on.
h. Select
Apply
.
6. Repeat
for all the relays you want to use.
More information
‣
Relay configuration example (page 81)
‣
Relay wiring and relay activation mode (page 81)
‣
‣
Testing relays in web interface (page 91)