Communication description
Register address
1 (1-based Modbus register number) = 0000
hex
(0-based register
address used in actual communication) based on the Modbus
Reference in
HMP4 User Guide
Data format
2 16-bit Modbus registers interpreted as IEEE 754 binary32
floating point value, least significant word first
Returned value
41F47AE1
hex
, which is binary32 representation of 30.56 (%RH)
Indigo 520 User Guide
M212287EN-A
76