Modbus Registers
The Modbus registers available for HMD65 include measurement output registers in metric and
non-metric units, pressure compensation setpoint configuration, status registers, and
communication test registers. For status registers, see
HMD65 User Guide
.
The Modbus communication settings are configured using the DIP switches on HMD65
component board: see
Modbus and BACnet Communication (RS-485) (page 16)
Registers are numbered in decimal, starting from one. Register
addresses in actual Modbus messages (Modbus Protocol Data Unit (PDU)) start
from zero.
Please check the reference documentation of your Modbus host (PLC) for the
notation of Modbus register addresses.
CAUTION!
16-bit integers have a maximum value of +32767. Certain measurement
parameters can exceed this value when x100 scaling is used (see measurement
registers 0100
hex
… 0107
hex
and 0180
hex
… 0187
hex
). Whenever possible, it is
recommended to use 32-bit float values.
Measurement Data Registers
Table 3 Modbus Measurement Data Registers (Read-Only)
Register
Number
(Decimal)
Address
(Hexadecimal)
Register Description
Data Format
Unit
Floating Point Values (Metric)
1
0000
hex
Relative humidity
32-bit float
%RH
0001
hex
3
0002
hex
Temperature
32-bit float
°C
0003
hex
5
0004
hex
Dew point temperature
32-bit float
°C
0005
hex
7
0006
hex
Dew/frost point
temperature
32-bit float
°C
0007
hex
9
0008
hex
Absolute humidity
32-bit float
g/m
3
0009
hex
11
000A
hex
Mixing ratio
32-bit float
g/kg
000B
hex
18
M212264EN-B
Summary of Contents for HMD60 Series
Page 4: ...4 M212264EN B ...
Page 22: ...22 M212264EN B ...
Page 94: ...94 M212264EN B ...
Page 97: ...Запрещается прикасаться к чувствительному элементу ОСТОРОЖНО 97 РУССКИЙ ...
Page 116: ...116 M212264EN B ...
Page 134: ...134 M212264EN B ...
Page 152: ...152 M212264EN B ...
Page 153: ......
Page 154: ...www vaisala com ...