DIP Switch Humidity Output Selection
Figure 10 HMD65 DIP Switch Example: T
df
Output Selected
RH
Relative humidity
Td
Dew point temperature
Tdf
Dew point/frost point temperature
A
Absolute humidity
X
Mixing ratio
Tw
Wet-bulb temperature
H
Enthalpy
You can change the humidity parameter that is output on the RH channel of HMD65 with the
DIP switches on the component board. Select the parameter you want the transmitter to
output by sliding the parameter's DIP switch to the right (
ON
). In the example in
, the selected output parameter is dew point/frost point temperature (T
df
). Keep the
other DIP switches in the
OFF
position (left).
The selected parameter uses the default scaling shown in
Table 2 HMD65 Default Parameter Scaling
Parameter
Default Scaling for 0 … 10 V Output Range
RH
0 … 100 %RH
T
d
-40 ... +80 °C (-40 ... +176 °F)
T
df
-40 ... +80 °C (-40 ... +176 °F)
A
0 … 300 g/m
3
(0 … 131.1 gr/ft
3
)
X
0 … 600 g/kg (0 … 4200 gr/lb)
T
w
-40 ... +80 °C (-40 ... +176 °F)
H
-40 … 1600 kJ/kg (-9.5 ... 695.6 Btu/lb)
If you need to change the default scaling of a parameter, configure the output
with Vaisala Insight PC software. See the instructions in
HMD65 User Guide
.
If you use the Insight software to further configure the output, note
that the DIP switch selections override the Insight configuration. When using
Insight to configure the output, set all humidity parameter DIP switches to the
OFF
position (left) to ensure they do not cause a conflict with the Insight
settings.
CAUTION!
15
ENGLISH
Summary of Contents for HMD60 Series
Page 4: ...4 M212264EN B ...
Page 22: ...22 M212264EN B ...
Page 94: ...94 M212264EN B ...
Page 97: ...Запрещается прикасаться к чувствительному элементу ОСТОРОЖНО 97 РУССКИЙ ...
Page 116: ...116 M212264EN B ...
Page 134: ...134 M212264EN B ...
Page 152: ...152 M212264EN B ...
Page 153: ......
Page 154: ...www vaisala com ...