Installation Manual Start-up Current Limiter VWZ 30/2 0020057445_00

Description of the device

2.1 Intended 

use

Vaillant geoTHERM heat pumps are state-of-the-art ap-
pliances which have been constructed in accordance 
with recognised safety regulations. However, there is a 
risk of death or serious injury to the user or third par-
ties or of damage to the device and other property in 
the event of improper use or use for which it is not in-
tended. 
This unit is not intended for use by persons (including 
children) having limited physical, sensory or mental ca-
pacities or who have inadequate experience and/or 
knowledge, unless supervised by a person responsible 
for their safety or who has been given instructions from 
them as to how to operate the unit.
Children must be watched to ensure that they do not 
play with the unit.
The start-up current limiter is intended exclusively for 
incorporation into heat pumps VWL 7C/9C, VWS/VWW 
61/2, 81/2, 101/2, 141/2, 171/2, 62/2, 82/2, 102/2 and VWS 
63/2, 83/2, 103/2, 64/2, 84/2, 104/2. Any other or addi-
tional use is considered to be improper. The manufac-
turer or supplier is not liable for any resulting damage. 
The user alone bears the risk.
Intended use includes the observance of the contents of 
the installation manual for the limiter.

a

 Caution!

Any improper use is forbidden!

The appliances must be installed by a qualified heating 
engineer, who is responsible for adhering to the existing 
regulations, rules and directives.

2.2 Scope 

of 

supply

The material supplied consists of:
–  Start-up current limiter PCB with wiring harness
– Installation manual

Safety information and regulations

3.1 Safety 

instructions 

The installation of the unit may only be undertaken by a 
recognised specialist, who will be responsible for 
adhering to the existing standards and regulations. He 
will also be responsible for proper installation and 
commissioning. Take note of the safety information in 
this ma-nual when installing the equipment!

e

 Danger!

Risk of electric shock!
Always switch off all power sources before car-
rying out electrical installation work. Make sure 
that they are secured against inadvertent 
switching on again.

a

 Caution!

Risk of damage!
The electrical installation may only be carried 
out by a recognised specialist company.

3.2 General 

requirements

3.2.1 

Preliminary remarks for room sealed appli-
ances

This appliance should only be installed in conjunction 
with either a Vaillant flue system or an alternative 
approved system (details of flue approval
categories can be found in the technical section of the 
installation manual).
Install the flue system as detailed in the separate flue 
installation instructions supplied with this boiler.

3.2.2 Related 

documents

The installation of the boiler must be in accordance with 
the relevant requirements of Gas Safety (Installation 
and Use) Regulations 1998, Health and Safety Document 
No. 635 (The Electricity at Work Regulations 1989), 
BS7671 (IEE Wiring Regulations) and the Water Supply 
(Water Fitting) Regulations 1999, or The Water Bylaws 
2000 (Scotland). It should also be in accordance with 
the relevant requirements of the Local Authority, 
Building Regulations, The Building Regulations 
(Scotland), The Building Regulations (Northern Ireland) 
and the relevant recommendations of the following Brit-
ish Standards:
–  BS 6700: Services supplying water for domestic use 

within buildings and their curtilages.

–  BS 6798: Specification for installation of gas fired 

boilers not exceeding 60 kW input.

–  BS 6891: Specification for installation of low pressure 

gas pipework up to 28 mm (R1) in domestic premises 
(2nd family gas).

–  BS 7593: Treatment of water in domestic hot water 

central heating systems.
Institute of Gas Engineers Publication IGE/UP/7/1998: 
”Guide for gas installations in timber framed housing”

Description of the device 2

Safety information and regulations 3

GB

Summary of Contents for VWZ 30/2 SV

Page 1: ...VWZ 30 2 SV ES GB HR RU SI UA...

Page 2: ......

Page 3: ...Para el instalador especializado Instrucciones de montaje Limitador de corriente de arranque para bombas de calor VWZ 30 2 SV ES...

Page 4: ...taci n vigente Vaillant declina toda responsabilidad por los da os que se produzcan debido a no respetar estas instruc ciones Documentaci n complementaria vigente VWS VWW 61 2 81 2 101 2 141 2 171 2 I...

Page 5: ...o por personal cualificado que ser responsable de que se respeten y tengan en cuenta las prescripciones regulaciones y directrices vi gentes 2 2 Volumen de suministro El volumen de suministro contiene...

Page 6: ...2 Fan Fan P Bn P Bn Vcoo Vcool Vc P Sw P Sw PComp Comp Co ICL ICL 230V 230V 23 N N N N Auf Auf Zu u Zu L L PE P P EP PE PE PE N N 1 1 2 2 1 1 2 2 1 1 2 2 2 1 1 2 2 1 1 2 2 1 1 2 2 2 DCF CF OT AF A Au...

Page 7: ...xi n del limitador de corriente de arranque en VWS VWW 61 2 81 2 101 2 141 2 171 2 y VWS 64 2 84 2 104 2 Leyenda 1 Instalar la platina debajo de la chapa de la instalaci n el ctrica 2 Retirar los puen...

Page 8: ...y VWS 63 2 83 2 103 2 Leyenda 1 Instalar la platina sobre la chapa de la instalaci n el ctrica 2 Retirar los puentes 3 Conectar la l nea de control 4 Conectar las l neas de conexi n Retire los tres p...

Page 9: ...rmes y aptos para la finalidad con la que se adquieren siempre y cuando se cumplan las siguientes condiciones 1 El aparato garantizado deber corresponder a los aparatos que el fabricante dise a expres...

Page 10: ...2 VWS VWW 62 2 VWS 63 2 VWS 64 2 VWS VWW 81 2 VWS VWW 82 2 VWS 83 2 VWS 84 2 VWS VWW 101 2 VWS VWW 102 2 VWS 103 2 VWS 104 2 VWS VWW 141 2 VWS VWW 171 2 Conexi n el ctrica 3 N PE 400V 50 Hz Corriente...

Page 11: ...For the installer Installation manual Start up current limiter for heat pumps VWZ 30 2 SV GB...

Page 12: ...and the environment h Note Useful information and instructions Symbol for a necessary task 1 3 Applicability of the manual This installation manual applies exclusively to equip ment with the followin...

Page 13: ...lso be responsible for proper installation and commissioning Take note of the safety information in this ma nual when installing the equipment e Danger Risk of electric shock Always switch off all pow...

Page 14: ...circulation hot water central heating systems for domestic premises Note only up to 45 kW BS 6880 Low temperature hot water heating sys tems of output greater than 45 kW Part 1 Fundamental and design...

Page 15: ...230 V 230 V 2 Fan Fan P Bn P Bn Vcoo Vcool Vc P Sw P Sw PComp Comp Co ICL ICL 230V 230V 23 N N N N Auf Auf Zu u Zu L L PE P P EP PE PE PE N N 1 1 2 2 1 1 2 2 1 1 2 2 2 1 1 2 2 1 1 2 2 1 1 2 2 2 DCF CF...

Page 16: ...Fig 4 2 Connecting the start up current limiter PCB to the VWS VWW 61 2 81 2 101 2 141 2 171 2 and VWS 64 2 84 2 104 2 Key 1 Fit the PCB underneath the electrical installation panel 2 Remove the jumpe...

Page 17: ...nd VWS 63 2 83 2 103 2 Key 1 Fit the PCB on to the electrical installation panel 2 Remove the jumpers 3 Connect the control cable 4 Connect the connecting cables Remove the three factory fitted jumper...

Page 18: ...Vaillant warranty Vaillant provide a full parts and labour warranty for this appliance The appliance must be installed by a suitably competent person in accordance with the Gas Safety Installation and...

Page 19: ...2 VWS 63 2 VWS 64 2 VWS VWW 81 2 VWS VWW 82 2 VWS 83 2 VWS 84 2 VWS VWW 101 2 VWS VWW 102 2 VWS 103 2 VWS 104 2 VWS VWW 141 2 VWS VWW 171 2 Electrical connection 3 N PE 400V 50 Hz Max start up curren...

Page 20: ......

Page 21: ...Za obrtnika Upute za monta u Ograni iva polazne struje za toplotnu crpku VWZ 30 2 SV HR...

Page 22: ...t e Opasnost ivotna opasnost od strujnog udara H Opasnost Opasnost od opeklina ili oparenja a Pozor Mogu a opasna situacija za proizvod i okoli h Napomena Korisne informacije i napomene Simbol neke po...

Page 23: ...i po tivanje uputa za monta u za ograni iva polazne struje a Pozor Svaka neprikladna primjena je nedopu tena Ure aje mora ugraditi stru ni obrtnik koji je odgovoran za po tivanje postoje ih propisa pr...

Page 24: ...P Sw P Sw PComp Comp Co ICL ICL 230V 230V 23 N N N N Auf Auf Zu u Zu L L PE P P EP PE PE PE N N 1 1 2 2 1 1 2 2 1 1 2 2 2 1 1 2 2 1 1 2 2 1 1 2 2 2 DCF CF OT AF A Auf Auf Zu u Zu PE PE EP N N L L L P...

Page 25: ...enje printane plo e ograni iva a polazne struje za VWS VWW 61 2 81 2 101 2 141 2 171 2 i VWS 64 2 84 2 104 2 Legenda 1 Montiranje printane plo e ispod lima elektroinstalacije 2 Odstranite premosnice 3...

Page 26: ...2 102 2 i VWS 63 2 83 2 103 2 Legenda 1 Montiranje printane plo e na lim elektroinstalacije 2 Odstranite premosnice 3 Priklju ite upravlja ki vod 4 Priklju ite priklju ne vodove Odstranite tri tvorni...

Page 27: ...predvi eno besplatno zbrinjavanje na komunalnom mjestu odlaganja otpada 5 2 Pakiranje Pobrinite se da se pakiranje odveze na prikladno mjesto za zbrinjavanje otpada 6 Jamstvo i servisna slu ba za kori...

Page 28: ...S 63 2 VWS 64 2 VWS VWW 81 2 VWS VWW 82 2 VWS 83 2 VWS 84 2 VWS VWW 101 2 VWS VWW 102 2 VWS 103 2 VWS 104 2 VWS VWW 141 2 VWS VWW 171 2 Elektri no priklju ivanje 3 N PE 400V 50 Hz Maks polazna struja...

Page 29: ...VWZ 30 2 SV RU...

Page 30: ...020057437 0020057436 VWS 64 2 84 2 104 2 0020057443 0020057442 1 1 1 2 d e H a h 1 1 2 1 1 2 1 2 2 1 3 3 1 4 3 2 3 2 1 3 2 2 3 3 3 3 1 3 3 2 3 4 4 4 1 VWL 7C 9C 4 4 2 VWS VWW 61 2 81 2 101 2 141 2 171...

Page 31: ..._00 1 3 VWZ 30 2 0020025744 1 1 1 4 Vaillant 40 40 2 2 1 Vaillant geoTHERM VWL 7C 9C VWS VWW 61 2 81 2 101 2 141 2 171 2 62 2 82 2 102 2 VWS 63 2 83 2 103 2 64 2 84 2 104 2 a 2 2 3 3 1 e a 3 2 Vaillan...

Page 32: ...30V 23 N N N N Auf Auf Zu u Zu L L PE P P EP PE PE PE N N 1 1 2 2 1 1 2 2 1 1 2 2 2 1 1 2 2 1 1 2 2 1 1 2 2 2 DCF CF OT AF A Auf Auf Zu u Zu PE PE EP N N L L L PE P P EZP N N L L L PE P P E SK2 P P N...

Page 33: ...64 2 84 2 104 2 1 h L3 L2 L3 L1 L2 L1 L1 L2 L3 L3 N N L3 N PE L1 L2 L3 L3 N N PE L1 L2 L3 N L1 L2 L3 L1 N PE L3 L2 L3 L2 L1 L3 L2 L1 1 ASB N L 2 1 8 A8 30 01 L1 L2 L3 L1 L2 L3 2 3 4 1 4 2 VWS VWW 61...

Page 34: ...82 2 102 2 VWS 63 2 83 2 103 2 1 h L1 L2 L3 L3 N N N N L1 L2 L3 L3 N N PE L1 L2 L3 N L1 L2 L3 L1 N PE L3 L2 1 ASB N L 2 1 8 L1 L2 L3 L1 L2 L3 N N L2 L1 L3 L1 L2 L3 L3 1 2 3 4 4 3 VWS VWW 62 2 82 2 102...

Page 35: ...Vaillant Vaillant Vaillant ElektroG 5 2 6 6 1 Vaillant Vaillant Vaillant Vaillant Vaillant Vaillant 2 Vaillant 10 VK VKK VKO GP 210 VU VUW VIH VRC 2 2 5 MAG VGH VER VES VEH VEN VEK VED 1 1 5 6 Vailla...

Page 36: ...9 C VWS VWW 61 2 VWS VWW 62 2 VWS 63 2 VWS 64 2 VWS VWW 81 2 VWS VWW 82 2 VWS 83 2 VWS 84 2 VWS VWW 101 2 VWS VWW 102 2 VWS 103 2 VWS 104 2 VWS VWW 141 2 VWS VWW 171 2 3 N PE 400 50 16A 26A 16A 40A 1...

Page 37: ...Za in talaterje Navodila za monta o Omejevalnik zagonskega toka za toplotne rpalke VWZ 30 2 SV SI...

Page 38: ...e Nevarnost ivljenjska nevarnost zaradi elektri nega udara H Nevarnost ivljenjska nevarnost zaradi elektri nega udara a Pozor Morebitna nevarna situacija za proizvod in oko lje h Napotek Koristne info...

Page 39: ...po rabnik prevzame vso tveganje Ustrezna uporaba vklju uje tudi upo tevanje navodil za monta o a Pozor Vsaka zloraba naprave je prepovedana Napravo mora namestiti strokovni in talater ki je odgo voren...

Page 40: ...Vcoo Vcool Vc P Sw P Sw PComp Comp Co ICL ICL 230V 230V 23 N N N N Auf Auf Zu u Zu L L PE P P EP PE PE PE N N 1 1 2 2 1 1 2 2 1 1 2 2 2 1 1 2 2 1 1 2 2 1 1 2 2 2 DCF CF OT AF A Auf Auf Zu u Zu PE PE...

Page 41: ...2 L3 2 3 4 1 Sl 4 2 Priklop omejevalnika zagonskega toka v VWS VWW 61 2 81 2 101 2 141 2 171 2 in VWS 64 2 84 2 104 2 Legenda 1 Namestite platino pod elektri no namestitveno plo o 2 Odstranite mosti k...

Page 42: ...82 2 102 2 in VWS 63 2 83 2 103 2 Legenda 1 Namestite platino na elektri no namestitveno plo o 2 Odstranite mosti ke 3 Priklju ite krmilni vod 4 Priklju ite priklju no napeljavo Odstranite tri tovarn...

Page 43: ...eno brezpla no odlaganje na komunalnih zbi ralnih mestih 5 2 Embala a Poskrbite da bo embala a za transport primerno od stranjena 6 Garancija in servisna slu ba 6 1 Tovarni ka garancija Garancija velj...

Page 44: ...2 VWS 63 2 VWS 64 2 VWS VWW 81 2 VWS VWW 82 2 VWS 83 2 VWS 84 2 VWS VWW 101 2 VWS VWW 102 2 VWS 103 2 VWS 104 2 VWS VWW 141 2 VWS VWW 171 2 Elektri ni priklju ek 3 N PE 400V 50 Hz Maks zagonski tok z...

Page 45: ...VWZ 30 2 SV UA...

Page 46: ...0051541 1 1 1 2 d e H a h 1 3 VWZ 30 2 0020025744 1 1 1 1 2 1 1 2 1 2 2 1 3 2 2 3 2 1 3 2 2 3 3 3 3 1 3 3 2 3 4 4 4 1 VWL 7C 9C 4 4 2 VWS VWW 61 2 81 2 101 2 141 2 171 2 VWS 64 2 84 2 104 2 5 4 3 VWS...

Page 47: ...3 VWZ 30 2 0020057445_00 2 2 1 geoTHERM VWL 7C 9C VWS VWW 61 2 81 2 101 2 141 2 171 2 62 2 82 2 102 2 VWS 63 2 83 2 103 2 64 2 84 2 104 2 a 2 2 3 3 1 e a 3 2 2 3 UA...

Page 48: ...30V 23 N N N N Auf Auf Zu u Zu L L PE P P EP PE PE PE N N 1 1 2 2 1 1 2 2 1 1 2 2 2 1 1 2 2 1 1 2 2 1 1 2 2 2 DCF CF OT AF A Auf Auf Zu u Zu PE PE EP N N L L L PE P P EZP N N L L L PE P P E SK2 P P N...

Page 49: ...64 2 84 2 104 2 1 h L3 L2 L3 L1 L2 L1 L1 L2 L3 L3 N N L3 N PE L1 L2 L3 L3 N N PE L1 L2 L3 N L1 L2 L3 L1 N PE L3 L2 L3 L2 L1 L3 L2 L1 1 ASB N L 2 1 8 A8 30 01 L1 L2 L3 L1 L2 L3 2 3 4 1 4 2 VWS VWW 61...

Page 50: ...82 2 102 2 VWS 63 2 83 2 103 2 1 h L1 L2 L3 L3 N N N N L1 L2 L3 L3 N N PE L1 L2 L3 N L1 L2 L3 L1 N PE L3 L2 1 ASB N L 2 1 8 L1 L2 L3 L1 L2 L3 N N L2 L1 L3 L1 L2 L3 L3 1 2 3 4 4 3 VWS VWW 62 2 82 2 102...

Page 51: ...057445_00 5 VWZ 30 2 Vaillant 5 1 Vaillant Vaillant Vaillant ElektroG 5 2 6 6 1 1 2 12 18 24 30 Vaillant Vaillant Vaillant 3 Vaillant Vaillant Vaillant 4 6 5 Vaillant 6 Vaillant 7 8 10 9 7 6 2 8 800 5...

Page 52: ...WS VWW 61 2 VWS VWW 62 2 VWS 63 2 VWS 64 2 VWS VWW 81 2 VWS VWW 82 2 VWS 83 2 VWS 84 2 VWS VWW 101 2 VWS VWW 102 2 VWS 103 2 VWS 104 2 VWS VWW 141 2 VWS VWW 171 2 3 N PE 400 50 16 A 26 A 16 A 40 A 16...

Page 53: ......

Page 54: ......

Page 55: ......

Page 56: ...0020057445_00 ES GB HR RU SI UA 10 2007...

Reviews: