Installation instructions VRT 392f 0020044239_01
10
Screen
Title
screen
Adjustable
operating values
(only display = A)
Remarks
Unit
Min.
value
Max.
value
Increment
Default
value
C1
HC1
Information
Target flow
temperature (A)
Flow temperature
target value
°C
1
C4
Hot water
information
Current target hot
water (A)
Target temperature of
hot water in cylinder
°C
1
Cylinder sensor 1 (A) Actual temperature of
hot water in cylinder
°C
1
Circulation pump
status (A)
On, Off
C9
HC1
parameters
Set-back
temperature
A set-back temperature
can be specified for the
periods between the
time windows.
°C
5
30
1
15
Control strategy
Determines the type of
room temperature
control
Two point represents
on/off control;
Similar to a modulating
control.
Two-point,
analogue
Two-point
Route matching
For optimum matching
to the size of the room
or radiator
arrangement.
(Positive values: slower
switching response of
controller;
negative values: faster
switching response of
controller).
-5
+5
1
0
C16
Hot water
parameters
Legionella protect
day
Day or block of days;
The cylinder is heated
up to 70°C for an hour
OFF, MO, TU,
WE, TH, FR,
SA, SU,
MO-SU
OFF
Start time of
Legionella
protection
0:00
24:00
0:10
4:00
C24
Service
Telephone number
Input of telephone
number for the
purposes of servicing
Changing the code
number
0000
9999
each 1
1000
Maintenance date
Day/Month/Year
adjustable
C25
Tools
Room temperature
correction
Adjustment of room
temperature sensor
R
-3
3
0,5
0
Display contrast
0
15
1
6
C26
Software versions
Software version
per module (A)
Display of version
number
Table 6.2 Screens in the expert technician operation level
10
6 Initial commissioning