Handing over to the end user 8
0020237057_01 Installation instructions
23
7.16
Selecting the wiring centre for
sensor/actuator test
Menu
→
Installer level
→
Sensor/actuator test
→
[Select
Unit]
–
This function allows you to select a connected wiring
centre for the sensor and actuator test. The system con-
trol lists the actuators and sensors for the selected wiring
centre. If you confirm the selection of an actuator using
OK
, the system control activates the relay. The actuator's
function can now be checked. Only the activated actuator
is active, all other actuators are "deactivated" at this time.
For example, you can move a mixing valve in the "Open"
direction and check that it is connected the right way round
or activate a pump and check that it starts up. If you select
a sensor, the system control shows the measured value of
the selected sensor. For the selected component, read the
measured values from the sensors and check whether the
individual sensors are providing the expected values (tem-
perature, pressure, flow rate, etc.).
7.17
Activating the screed-drying function
Note
All heat pumps except for the hybrid heat pump
are used for screed drying.
Menu
→
Installer level
→
Screed-drying function
→
HEAT-
ING1
–
You can use this function to "dry heat" freshly laid screed
in accordance with the construction regulations, accord-
ing to a defined time and temperature schedule.
When screed drying is activated, all the selected operating
modes are interrupted. The system control controls the flow
temperature of the controlled heating circuit according to a
pre-set program, regardless of the outdoor temperature.
Days after starting the func-
tion
Target flow temperature for
this day [°C]
1
25
2
30
3
35
4
40
5
45
6 - 12
45
13
40
14
35
15
30
16
25
17 - 23
10 (frost protection function,
pump in operation)
24
30
25
35
26
40
27
45
28
35
29
25
The display shows the current day and the target flow tem-
perature. You can manually set the current day.
The day is always changed at 00:00, irrespective of when
the function starts.
After a mains Off/On, screed drying starts with the last active
day.
The function ends automatically when the last day of the
temperature profile has elapsed (day = 29) or if you set the
start day to 0 (day = 0).
7.18
Changing the code for Installer level
Menu
→
Installer level
→
Change code
–
You can use this function to change the access code for
the
Installer level
.
If the code is no longer available, you must reset the system
control to the factory setting in order to obtain access to In-
staller level again.
Resetting to factory setting (
→
Page 11)
8
Handing over to the end user
8.1
Handing the product over to the end user
▶
Inform the operator of how to handle and operate their
product.
▶
Provide the operator with all relevant instructions and unit
documentation for safe-keeping.
▶
Tell the operator the article number of the product.
▶
Go through the operating instructions with the operator .
▶
Answer any questions the end user may have.
▶
In particular, draw the end user's attention to the safety
information that they must follow.
Danger!
Risk of death from legionella.
Legionella multiply at temperatures below
60 °C.
▶
Ensure that the end user is familiar with
all of the Anti-legionella measures in order
to comply with the applicable regulations
regarding legionella prevention.
▶
Point out the anti-legionella function to the end user.
▶
Inform the end user that they must have the product
maintained in accordance with the specified intervals.
▶
Advise the end user that the system control may not work
as well as it should do if it is removed from its intended
installation site.
▶
Inform the end user that the reception strength between
the radio receiver unit and the system control or outdoor
temperature sensor is not affected by electrical devices
or building components.