Detecting and rectifying faults
Fault
Possible cause
Remedy
No flow rate at the water
tap
1.
The cold-water isolation valve is closed.
2.
The main filter is blocked.
3.
The pressure reducer is not installed correctly.
1.
Check and open the cold-water isolation valve.
2.
Close the cold-water isolation valve, and clean
the filter and the pressure reducer.
3.
Check whether the pressure reducer has been
installed correctly.
Low flow rate and pres-
sure at a water tap
1.
The filter in the cold water pipe is clogged.
1.
Close the cold-water isolation valve, and clean
the pressure reducer filter.
Water from the water tap
is cold
1.
The cylinder was not started up.
2.
The cold-water isolation valve is not fully open.
3.
The heat generator is not operating.
4.
The thermal cut-out for a system component
has been triggered.
5.
The 2-port motorised valve is defective.
6.
The immersion heater is defective.
1.
Open all of the relevant valves.
2.
Check the thermostat or the room thermostat
and, if required, set this.
3.
Check the heat generator to see if a fault code
is present.
4.
Check and initialise the cylinder.
5.
Check the connections for the 2-port motorised
valve.
Domestic hot water
temperature at the water
tap too high
1.
The thermostat is set too high.
2.
The thermostatic valve is not present or is
defective.
1.
Check the target temperature. It must be
between 60 and 65 °C.
2.
Install a mixer valve.
3.
Check the cabling. Repair the cable.
4.
Reduce the temperature of the thermostat to
60 °C.
5.
Replace the thermostatic valve.
Irregular domestic hot
water output at the water
tap
1.
The expansion vessel is defective.
2.
The thermal cut-out for a system component
has been triggered (thermal control).
1.
Compare the temperature between the con-
trols. The maximum temperature has priority.
2.
If required, adjust the pre-charge pressure.
3.
Interrupt the power supply to the product and
the heat generator. Check the thermal cut-outs
for the system components and replace these
in the event of a defect.
VIH .. .../3 MR only
The control panel does
not display any func-
tions.
1.
The power supply is interrupted.
1.
Reconnect the power supply.
2.
Check the plug connection.
VIH .. .../3 MR only
F.01/F.02
1.
Interruption in the cable for the top (
F.01
) or
bottom (
F.02
) cylinder temperature sensor
2.
Top (
F.01
) or bottom (
F.02
) cylinder temperat-
ure sensor is defective.
1.
Check the cable for the cylinder temperature
sensor.
2.
Replace the cable harness.
VIH .. .../3 MR only
F.03
1.
The external current anode is defective.
2.
The cylinder is corroded.
1.
Check the electrical connections.
2.
Replace the external current anode.
3.
Replace the cylinder.
B
Inspection and maintenance work
–
Overview
The table below lists the manufacturer requirements with respect to minimum inspection and maintenance intervals. If na-
tional regulations and directives require shorter inspection and maintenance intervals, you should observe these instead of
the intervals listed.
#
Maintenance work
Interval
1
Check the connections for tightness (visual inspection).
Annually
2
Check the temperature and pressure relief valve (by actuating it)
Annually
3
Check the pressure in the expansion vessel (annual manometer).
Annually
4
Check the tightness of the flange in the cleaning eye (visual inspection)
Annually
5
Check the state of wear of the magnesium protection anode
Annually
6
Clean the cylinder
Annually
7
Check the contacts of the external current anode for corrosion
Annually
Summary of Contents for VIH R 3 .R Series
Page 29: ...1 0020241666_05 29 1 1 1 1 2 85 C IP 1 3 1 3 1 Vaillant Group 1 3 2...
Page 30: ...1 30 0020241666_05 3 mm 3 1 3 3 1 3 4 1 3 5 1 3 6 1 4...
Page 32: ...6 32 0020241666_05 6 1 2 3 4 5 6 7 7 1 33 7 2 8 1 2 3 4 5 9 10...
Page 34: ...34 0020241666_05 B 1 2 3 4 5 6 7...
Page 82: ...1 82 0020241666_05 1 1 1 1 2 85 C IP 1 3 1 3 1 Vaillant Group 1 3 2 3 mm 3 1 3 3 1 3 4...
Page 83: ...1 0020241666_05 83 1 3 5 1 3 6 1 4...
Page 85: ...7 0020241666_05 85 7 7 1 86 7 2 8 1 2 3 4 5 9 10...
Page 100: ...1 100 0020241666_05 1 1 1 1 2 85 C IP 1 3 1 3 1 Vaillant Group 1 3 2...
Page 101: ...1 0020241666_05 101 3 mm 3 1 3 3 1 3 4 1 3 5 1 3 6 1 4...
Page 103: ...7 0020241666_05 103 4 5 6 7 7 1 104 7 2 8 1 2 3 4 5 9 10...
Page 105: ...0020241666_05 105 3 4 5 6 7...
Page 133: ...1 0020241666_05 133 1 1 1 1 2 85 C c IP 1 3 1 3 1 Vaillant Group Rus...
Page 134: ...1 134 0020241666_05 1 3 2 3 3 1 3 3 1 3 4 1 3 5 1 3 6 1 4...
Page 136: ...6 136 0020241666_05 6 1 2 3 4 5 6 7 7 1 137 7 2 8 1 2 3 4 5 9 10...
Page 138: ...138 0020241666_05 3 4 5 6 7...
Page 177: ...1 0020241666_05 177 1 1 1 1 2 85 C IP 1 3 1 3 1 Vaillant Group...
Page 178: ...1 178 0020241666_05 1 3 2 3 3 1 3 3 1 3 4 1 3 5 1 3 6 1 4...
Page 180: ...6 180 0020241666_05 6 1 2 3 4 5 6 7 7 1 181 7 2 8 1 2 3 4 5 9 10...
Page 182: ...182 0020241666_05 5 6 7...
Page 185: ...1 0020241666_05 185 1 4...