Source regeneration:
The system control switches the
Cooling
function on and guides
the heat from the living room back to the earth via the heat pump.
Prerequisite:
–
The
Automatic cooling:
function has been activated.
–
The
Absence
function is active.
Factory setting:
No
Current room air humidity: %rel
Current room air humidity, measured using the installed humidity
sensor
Current dew point: °C
The system control calculates the current dew point in the living
room.
Hybrid manager:
Factory setting:
Bival. point
triVAl
The heat generator is selected based on the set tariffs in relation
to the heat demand.
Bival. point
The heat generator is selected based on the outdoor temperature
(
Heating bivalence point: °C
and
Alternative point:
).
Heating bivalence point: °C
If the outdoor temperature falls below the set value, the system
control enables the back-up boiler to operate in parallel with the
heat pump in heating mode.
Prerequisite:
Bival. point
is selected in the
Hybrid manager:
function.
Factory setting: -5 °C
DHW bivalence point: °C
If the outdoor temperature falls below the set value, the system
control activates the back-up boiler in parallel with the heat pump.
Factory setting: -7 °C
Heating alternative point: °C
If the outdoor temperature falls below the set value, the system
control switches the heat pump off and the back-up boiler meets
the heat demand in heating mode.
Prerequisite:
Bival. point
is selected in the
Hybrid manager:
function.
Factory setting:
Off
DHW alternative point: °C
If the outdoor temperature falls below the set value, the system
control switches the heat pump off and the back-up boiler meets
the heat demand in domestic hot water mode.
Factory setting:
Off
LHM temperature: °C
Set a low target flow temperature. If the heat pump fails, the back-
up boiler fulfils the heat demand, which leads to higher heating
costs. The end user should recognise that heat loss means that
there is a problem with the heat pump.
The end user can use the
Mode: Temporary mode: Back-up
heater
function to enable the back-up boiler and therefore deac-
tivate the target flow temperature that is set here.
Factory setting: 25 °C
Back-up boiler type:
Select a type for the heat generator that is also installed. An incor-
rect selection may lead to increased costs.
Prerequisite:
triVAl
is selected in the
Hybrid manager:
function.
Factory setting:
Condensing
Summary of Contents for sensoCOMFORT VRC 720/3
Page 2: ...2 en Operating and installation instructions 3 en Country specifics 59...
Page 38: ...38 Operating and installation instructions 0020334316_02 4 9 2 3 Wiring diagram 0020184677...
Page 44: ...44 Operating and installation instructions 0020334316_02 4 9 4 5 Wiring diagram 0020177912...
Page 47: ...0020334316_02 Operating and installation instructions 47 4 9 5 5 Wiring diagram 0020280010...
Page 50: ...50 Operating and installation instructions 0020334316_02 4 9 6 5 Wiring diagram 0020260774...
Page 61: ......
Page 62: ......
Page 63: ......