![Vaillant recoVAIR VAR 60/1 D Installation Instructions Manual Download Page 46](http://html.mh-extra.com/html/vaillant/recovair-var-60-1-d/recovair-var-60-1-d_installation-instructions-manual_848846046.webp)
Appendix
44
Installation instructions recoVAIR 0020236694_04
Appendix
A Technical data
Technical data
–
General
* Required for operation
VAR 60/1 D
VAR 60/1 DW
Flow rate
30/45/60 m
3
/h
30/37.5/45/52.5/60
m
3
/h
Power consumption
4.9 … 8.9 W
4.9 … 8.9 W
Specific power consumption
0.3 W/(m
³
/h)
0.3 W/(m
³
/h)
Sound power level
33.8 … 45.8 dB(A)
33.8 … 45.8 dB(A)
Sound pressure level, clearance
1 m
25.8 … 37.7 dB(A)
25.8 … 37.7 dB(A)
Heat recovery efficiency
85%
85%
Sound reduction index of the
open wind guard
36 dB
36 dB
Sound reduction index of the
closed wind guard
40 dB
40 dB
Filter class
2 x G3
2 x G3
Frequency range
−
863 … 870 MHz
Transmission power
−
<10 mW
Weight
1.5 kg
1.5 kg
Outdoor temperature*
−
20 … 50
℃
−
20 … 50
℃
Air humidity outdoors*
0 … 100 %
0 … 100 %
Technical data
–
Electrics
VAR 60/1 D
VAR 60/1 DW
Supply voltage
220 … 240 V
AC
220 … 240 V
AC
Frequency
50 Hz
50 Hz
Max. current load
38.6 mA
38.6 mA
Level of protection
IPX4
IPX4
Summary of Contents for recoVAIR VAR 60/1 D