40
Installation and maintenance instructions 0020213394_05
D
Dual-circuit power supply special tariff A
–
3~/N/PE 400 V (wiring diagram 2 =
)
N
L1
X102
X110A
X110B
X101
X103
X110
N L3 L2 L1
L3
L2
L1
L1 L2 L3 N
7
6
5
1
2
3
1
Continuous power supply for internal auxiliary elec-
tric heating
2
Power supply for control system
3
Blocked power supply
X110A
Optional power output for controller PCB (X110)
X110B
Optional power output for controller PCB (X110)
X101
Mains connection for compressor
X103
Optional power output for internal auxiliary electric
heating (X102)
X102
Mains connection for internal auxiliary electric heat-
ing
X110
Mains connection for heat pump controller PCB
In this case, the heat pump is operated using two electricity tariffs (two consumption meters).
A continuous power supply ensures the operation of the internal electric back-up heater and the control PCB of the heat
pump via its own electricity meter.
The power from the additional, blockable power supply for the compressor is supplied via a second electricity meter and can
be suspended by the power supply network operator at peak times. The duration and frequency of the outage is determined
by the power supply network operator or must be clarified with them.