Maintenance and care 6

0020213396_02 flexoTHERM exclusive Operating instructions

13

6 Maintenance and care

6.1 Fulfilling requirements for the

installation site

The installation site must be dry and frost-
proof throughout.

Conditions

: Outdoor air heat source

The air/brine collector is designed to be
operated with outdoor air. The air intake
and blow-off route of the outdoor unit must
be kept clear at all times in order to guar-
antee that the air can flow unhindered and
as intended. Vegetation and, in winter,
snowfall, must be cleared.
You are not permitted to make any sub-
sequent structural alterations which
may result in a reduced room volume
or a change to the temperature at the
installation site.

6.2 Caring for the product

Caution.
Risk of material damage
caused by unsuitable clean-
ing agents.

Do not use sprays, scouring
agents, detergents, solvents
or cleaning agents that con-
tain chlorine.

Clean the casing with a damp cloth and
a little solvent-free soap.

6.3 Reading maintenance

messages

If the

symbol is shown in the display,

the product requires maintenance work.
The product is not in fault mode; it contin-
ues to operate.

Consult a competent person.

6.4 Checking the system pressure

Check the filling pressure of the heating
installation every day for a week after
initial start-up and maintenance work,
and then twice a year.

Filling pressure:

0.07 MPa

(

0.70 bar)

Filling pressure too low

Inform your competent person so
that he can add heating water and
increase the filling pressure.

6.5 Checking the brine circuit's

filling pressure

Check the brine circuit's filling pressure
at regular intervals. Read the brine cir-
cuit's filling pressure in the heat pump's
display.

Brine fluid operating pressure range:
0.07 … 0.20 MPa (0.70 … 2.00 bar)

7 Troubleshooting

7.1 Fault message

Note

If the heat pump has switched off
automatically due to a fault, the
system controller can be used to
activate a limp home mode with the
electric auxiliary heating.

If several faults occur at the same time,
the display shows the corresponding fault
messages for two seconds each in alterna-
tion.

F.714 Environment circuit: Pressure too
low

If the filling pressure falls below the min-
imum pressure, the heat pump will be
switched off automatically.

Minimum brine fluid pressure:

0.05 MPa (

0.50 bar)

Min. brine fluid operating pressure:

0.07 MPa (

0.70 bar)

Summary of Contents for flexoTHERM exclusive VWF 87/4

Page 1: ...ctions flexoTHERM exclusive VWF 57 197 4 VWF 57 117 4 230V GB IE Operating instructions Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810...

Page 2: ...he product 12 5 6 Adjusting the target cylinder temperature 12 5 7 Yield indicator 12 5 8 Displaying the Live Monitor 12 5 9 Displaying the building circuit pressure 12 5 10 Displaying the environment...

Page 3: ...he system is intended as a heat generator with cooling function for closed heating installations and for hot wa ter generation Operation of the pump outside the applica tion limits results in the heat...

Page 4: ...vided in these operating instructions 1 3 2 Risk of death due to explosive and flammable materials Do not use or store explosive or flammable materials e g petrol paper paint in the in stallation room...

Page 5: ...ed out at all Never attempt to carry out maintenance work or repairs on your product yourself Faults and damage should be immediately rectified by a competent person Adhere to the maintenance interval...

Page 6: ...ulations Ensure that only officially cer tified competent persons with appropriate protective equip ment carry out maintenance work on the refrigerant circuit or access it Arrange for the refriger ant...

Page 7: ...ure use 2 3 Applicability of the instructions These instructions apply only to Applicability Great Britain OR Ireland Product VWF 57 4 VWF 87 4 VWF 117 4 VWF 157 4 VWF 197 4 Applicability Great Britai...

Page 8: ...is located on a plate be hind the front flap The 7th to 16th digits of the serial number form the article number 4 3 Opening the front flap 1 Take hold of the recessed handle in the front flap on the...

Page 9: ...f and a fault message is displayed 4 6 5 Pump and valve blocking protection system This function prevents the pumps for heat ing water and brine and all diverter valves from sticking The pumps and the...

Page 10: ...ade to start the auxiliary electric heating A fault mes sage is displayed that can only be reset by pressing the Reset button or by switching the heat pump off and on again Max heating circuit tempera...

Page 11: ...a change to a set value Going one selection level higher Confirm setting Going one selection level lower Op erator control element Function at the same time Calling up the menu or Reducing or increas...

Page 12: ...Monthly values may vary considerably since for example in the summer only hot water generation is used A large num ber of factors influence this estimate e g the type of heating installation direct he...

Page 13: ...nance work The product is not in fault mode it contin ues to operate Consult a competent person 6 4 Checking the system pressure Check the filling pressure of the heating installation every day for a...

Page 14: ...itches to disconnect the product from the power supply 8 1 2 Protecting the product against frost Observe the installation site require ments for the product Page 13 8 2 Permanently decommissioning th...

Page 15: ...t ent person to the prevailing building regu lations at the time of installation G3 All appliances shall be fully commissioned in accordance with our installation manual and Benchmark commissioning ch...

Page 16: ...ue kWh Working figure Total Heating Cumulative value Energy yield Month Domestic hot water Cumulative value kWh Working figure Month Domestic hot water Cumulative value Energy yield Total Domestic hot...

Page 17: ...cted as delivered condition Heating rod power Current value kW Information Contact data Phone number Serial number Permanent value Operating hours total Cumulative value h Hours heating Cumulative val...

Page 18: ......

Page 19: ......

Page 20: ...ire DE56 1JT Telephone 0330 100 3461 info vaillant co uk www vaillant co uk These instructions or parts thereof are protected by copyright and may be reproduced or distributed only with the manufactur...

Reviews: