0020213395_04 Installation and maintenance instructions
47
Code
Meaning
Cause
Remedy
F.710
Env. circuit: Outlet temp. too low
–
Environment circuit pump defective
–
Temperature sensor for environment
circuit outlet defective
–
Volume flow too low in the environ-
ment circuit
–
Air in the environment circuit
–
Device Specific Number (DSN) set-
ting was not applied when replacing
the control PCB (HMU)
–
Freeze protection setting was not
applied when replacing the control
PCB (HMU)
–
Check the flow rate in the environ-
ment circuit
–
Check the quality of the plug contact
on the PCB and on the cable har-
ness
–
Check that the sensor is working
correctly (resistance measurement
using sensor characteristic values)
–
Replace the sensor
–
Check the volume flow of the en-
vironment circuit pump (optimum
spread of 3 K)
–
Purge the environment circuit
–
Always check the Device Specific
Number (DSN) setting
–
Check the set value for the freeze
protection in accordance with the en-
vironment circuit type on the control
panel
F.714
Environment circuit: Pressure too
low
–
Pressure loss in the environment
circuit due to leakages or air pockets
–
Environment circuit pressure sensor
defective
–
Check the environment circuit for
leaks
–
Top up the medium (brine-to-water),
purge
–
Check the quality of the plug contact
on the PCB and on the cable har-
ness
–
Check that the pressure sensor is
working correctly
–
Replace the pressure sensor
F.715
Env. circuit: Fault contact: Pump
open
–
The electronics system of the high-
efficiency pump has detected a fault
(e.g. dry running, blockage, dirt,
overvoltage, undervoltage) and has
switched off and locked the pump.
–
Air in the environment circuit
–
Brine fluid viscosity is too high
–
Switch the heat pump off for at least
30 seconds (no current)
–
Check the quality of the plug contact
on the PCB
–
Check that the pump functions cor-
rectly
–
Purge the environment circuit
–
Use a refractometer to check the
mixture ratio of the brine fluid
–
Check the dirt filter/strainer for dirt
–
Check the air separator
F.718
Fan unit 1: Fan blocked
–
There is no confirmation signal stat-
ing that the fan is rotating
–
Check the air route and, if required,
remove any blockages
–
Check and, if required, replace the
F1 fuse on the PCB in the fan unit
(OMU)
F.719
Fan unit 1: Safety cut-out open
–
The safety cut-out on the de-icer is
open due to insufficient volume flow
and/or brine temperatures above
70 °C
–
When operating the de-icer outside
of the permitted area of application
–
De-icer operation when the brine
circuit is not filled
–
De-icer operation at brine tem-
peratures above 120 °C trips the
safety fuse of the safety cut-out
and requires that the fuse be re-
placed
–
Check for circulation in the environ-
ment circuit pump
–
If required, open the stopcocks
The safety cut-out is automatically reset
as soon as the temperature at the fuse
falls below 55 °C again.
If the safety cut-out is still open at a de-
icer temperature below 55 °C, temper-
atures above 120 °C were reached and
the safety fuse tripped.
–
Check and, if required, replace the
F1 fuse of the air/brine collector
–
Replace the safety cut-out
F.723
Building circuit: Pressure too low
–
Pressure loss in the building circuit
due to leakages or air pockets
–
Building circuit pressure sensor de-
fective
–
Check the building circuit for leaks
–
Top up with water, purge
–
Check the quality of the plug contact
on the PCB and on the cable har-
ness
–
Check that the pressure sensor is
working correctly
–
Replace the pressure sensor