background image

15

Instructions for installation and servicing ecoTEC / 839592_09

 

3.10  Guide to system requirements

3.10.1    Water circulation system

Detailed recommendations for the water circulation sys-
tem are given in BS 6798 and BS 5449: Part 1 (for small 
bore and micro bore central heating systems). Pipework 
not forming part of the useful heating surface should be 
insulated to help prevent heat loss and possible freezing, 
particularly where pipes are run through roof spaces 
and ventilated underfloor spaces. Draining taps must be 
located in accessible positions which permit the draining 
of the whole system including the boiler and the hot 
water system. Draining taps should be at least 1/2 in. 
BSP nominal size and be in accordance with BS 2879.
The boiler is suitable for use with minibore or microbore 
systems. Copper tubing to BS 2871: Part 1 should be used 
for water carrying pipework. All capillary joints in all 
DHW pipework must be made with lead free solder. 
Particularly where a new boiler is to be fitted to an exist-
ing system, it is good practice that the system is thor-
oughly cleansed.

 Caution!

To prevent the formation of deposits and pre-
vent serious damage to the appliance and sys-
tem, cleansers must be used carefully and must 
be completely removed by thoroughly flushing 
the system. Cleansers should only be left in 
systems for a maximum of 24 hours.

This cleansing must take place prior to the fitting of the 
new boiler and be in accordance with BS 7593. For 
advice on the application of system cleansers contact 
Sentinel, Betz Dearborn Ltd. Widnes, Cheshire, WA8 
8UD. Tel: 0151 420 9595, or Fernox, Alpha Fry 
Technologies, Tandem House, Marlow Way, Croydon, CR0 
4XS. Tel 0870 8700362.

3.10.2   Filling and preparing heating system

The system can be filled using the built in filling loop 
(ecoTEC plus combination boilers only) or via a separate 
filling point fitted at a convenient position on the heat-
ing circuit. The connection must be removed when filling 
is completed. Where local Water Authority regulation 
does not allow temporary connection, a sealed system 
filler pump with break tank must be used. The heating 
system will not be filled automatically from the domes-
tic hot water side. (Alternative methods of filling sealed 
systems are given in BS 5449).

3.10.3   Pressure relief valve

A pressure relief valve is provided with the boiler. This 
safety device is required on all sealed C.H. systems and 
is preset at 3 bar and provided with a 15 mm compres-
sion connection for a discharge pipe, which must be of 
no less than 15 mm in diameter. The pressure relief 
valve must not be used for draining purposes.

3.10.4   Pressure gauge

This is factory fitted to the boiler and indicates the pri-
mary circuit pressure to facilitate filling and testing.

3.10.5   Expansion vessel

ecoTEC boilers incorporate a 10 litre expansion vessel 
which is suitable for a sealed heating system with a 
maximum water content of 100 litres.
If the nominal capacity of the built in expansion vessel is 
not sufficient for the heating system (for instance in 
case of modernisation of old open systems) an addition-
al expansion vessel can be installed external to the boil-
er. It should be fitted in the return pipe as close as pos-
sible to the boiler in accordance with BS 5449: Part 1.
Guidance on the sizing of an additional expansion vessel 
is given in Table 3.5.

Vessel Volume [L]

Initial system pressure (bar)

1.0

1.5

Pressure relief valve setting (bar)

3.0

Total water content of system litres

25

2.7

3.9

50

5.4

7.8

100

10.9

15.6

125

13.6

19.5

150

16.3

23.4

175

19.1

27.3

200

21.8

31.2

225

24.5

35.1

250

27.2

39.0

275

30.0

42.9

300

32.7

46.8

325

35.7

50.7

350

38.1

54.6

375

40.9

58.5

400

43.6

62.4

425

46.3

66.3

450

49.0

70.2

475

51.8

74.1

500

54.5

78.0

For system volumes other than those given 
above, multiply the system volume by the 
factor across

0.109

0.156

Table 3.5  Sizing of additional expansion vessel

3.11 Pump 

specifications

3.11.1  Circulating pump

only ecoTEC plus:

The circulating pump is included in the boiler. The residual 
pump discharge height depending on the by-pass valve is 
shown in Fig. 3.10.1 (ecoTEC plus) and 3.10.2 (ecoTEC plus 
637 / 837).
The operating mode of the 2-step pump can be adjusted 
below the diagnosis number “

d.19

”, see section 8.1.2.

General requirements 3

Summary of Contents for ecoTEC pro 24

Page 1: ...5 ecoTEC plus 618 ecoTEC plus 624 ecoTEC plus 630 ecoTEC plus 637 ecoTEC plus 824 ecoTEC plus 831 ecoTEC plus 837 ecoTEC pro 28 ecoTEC pro 24 Instructions for installation and servicing ecoTEC Wall hu...

Page 2: ...onnection 22 4 12 2 Pressure Relief Valve 23 4 13 Connecting the flue system to the boiler 23 4 14 Electrical connection 23 4 14 1 General requirements 23 4 14 2 Connection to the main supply 24 4 14...

Page 3: ...ning the boiler 41 7 6 Test operation 41 8 Troubleshooting 41 8 1 Logical fault finding procedure 41 8 1 1 Status codes 41 8 1 2 Diagnostic codes 42 8 1 3 Fault codes 45 8 1 4 Fault memory 45 8 4 Test...

Page 4: ...hot water is supplied directly from the boiler without requiring a copper cylinder cold water tank feed and expansion vessel and associated pipework Domestic hot water has priority over central heati...

Page 5: ...to the inspec tion and maintenance conditions Danger Any incorrect use is forbidden The appliances must be installed by a competent person who is responsible for adhering to the existing regula tions...

Page 6: ...load 80 C flow 60 C return 40 74 40 83 40 70 40 74 40 74 C C NOx class 5 Protection class IP X4D max flow temperature 85 C Adjustable flow temperature Default setting max 75 C 30 85 40 85 30 85 C Max...

Page 7: ...8 13 9 5 7 17 1 g s g s Exhaust temperature at minimum thermal load 40 C flow 30 C return at maximum thermal load 80 C flow 60 C return 40 70 40 75 40 83 40 70 C C NOx class 5 Protection class IP X4D...

Page 8: ...ination boilers only 3 Gas connection 15mm 4 Hot water connection 15mm combination boilers only 5 Heating flow pipe 22mm 6 Hanging bracket 7 Flue hole flue system 60 100 8 Flue hole flue system 80 125...

Page 9: ...ctronics box 10 Pressure sensor 11 Hot water heat exchanger 12 Gas valve 13 Heat exchanger 14 Flue pipe connection 2 4 Type plate The type plate of the Valliant ecoTEC is attached to the bottom of the...

Page 10: ...ssors on industrial and commercial premises IG UP 7 Edition 2 Gas installations in timber framed and light steel framed buildings IGE UP10 Installation of gas appliances in industrial and commercial p...

Page 11: ...tank and ventilation above Fig Table 3 1 Contents included with delivery of ecoTEC plus system boilers 1 2 3 4 6 5 7 8 Fig 3 2 Contents included with delivery of ecoTEC plus combination boilers DO NO...

Page 12: ...y for this purpose An existing cupboard or compartment may be used provided that it is modified for the purpose Details of essential features of cupboard compartment design including airing cupboard i...

Page 13: ...increase siting flexibility 8 4 1456 542 901 Fig 3 5 Art No 0020060570 3 6 2 Optional 125mm flue system A concentric flue system of 125mm outside diameter is available and can be used to achieve flue...

Page 14: ...t affecting the performance of the boiler In order to ensure that the condensate plume does not affect adjacent surfaces the terminal should be extended as shown in Fig 3 9 2 Dimension F This clearanc...

Page 15: ...ary connection a sealed system filler pump with break tank must be used The heating system will not be filled automatically from the domes tic hot water side Alternative methods of filling sealed syst...

Page 16: ...is shown in Fig 3 11 400 300 200 100 0 0 200 400 600 800 1000 1200 1600 Lift mbar Volumeflow l h 1800 1400 Fig 3 11 Pump specifications ecoTEC pro 3 11 2 System by pass An automatic system by pass is...

Page 17: ...ean forward sideways Clear the route before attempting the lift If removing boiler from truck strad dle the load and tilt forwards to facilitate secure grip Ensure safe lifting techniques are used kee...

Page 18: ...lift when removed from the carton Obtain firm grip on front and sides of appliance lift upwards ensure stable balance achieved and lift upwards to drop into place onto brack et If 2 persons positioni...

Page 19: ...the hanging bracket Note Use alternative fixing holes where necessary 4 3 Flue exit If using rear flue mark the position of the air flue duct and its circumference Other flue options Flue instructions...

Page 20: ...cinder hemp putty rust rough dust and similar sub stances are removed from the pipes Otherwise such substances can be deposited in the appli ance and cause damage The appliance is fitted with an expan...

Page 21: ...r connection Fit the union nut 4 and the compression olive 3 to the pre formed tail provided with ecoTEC plus appli ances 5 The diameter of the pipe is 15mm Fully insert the pre formed tail into the s...

Page 22: ...f freezing and should not be more than 3m d at a condensate absorption point soakaway 7 The external pipe length should not be more than 3m Refer to BS 6798 Specification for installation of gas fired...

Page 23: ...3 Fig 4 12 Installing the drain pipe on the pressure release valve of the heating system picture shows ecoTEC plus combination boiler The pressure release valve for the heating system is integrated i...

Page 24: ...ct any power voltage to the con nections 7 8 9 or BUS Note Ensure that all cords pass through the cable clamps in the rear of the control box and are securely fixed Ensure that the power supply is con...

Page 25: ...50 Hz remove bridge on connection Heating pump With ecoTEC pro 1 step pump plug with 3 pin With ecoTEC plus 2 step pump plug with 5 pin Mains supply 230 V 50 Hz 2A fuse slow Igniter Caution Do not co...

Page 26: ...ck X 20 7 black X 20 8 blue X 2 12 green X 2 11 red X 2 9 black Pump X 20 18 red 24 VDC X 20 9 blue earth X 20 16 blue earth X 20 13 black X 20 12 black X 20 4 grey PWM X 20 3 black Hall signal X 20 1...

Page 27: ...e sensor NTC return X 20 5 red X 20 7 black X 20 7 black X 20 8 blue X 2 10 black X 2 14 brown X 2 12 green X 2 11 red X 2 9 black Pump X 20 18 red 24 VDC X 20 9 blue earth X 20 16 blue earth X 20 13...

Page 28: ...nd 4 Terminal 5 is an additional neutral connection for external neutrals such as from the anticipator of a room thermostat 4 15 3 Connection details for external time switches and boiler terminal str...

Page 29: ...switches off 4 19 Anticycling economiser control The boiler incorporates a built in anticycling control to ensure that energy wasteful short cycling of the boiler cannot occur This control prevents th...

Page 30: ...d bleeding the heating system Note The P 6 test program is for filling the heating system The diverter valve combination boilers only moves to the centre position the pump does not run and the applian...

Page 31: ...mostat valves Check if both stop valves on the heater are open Only in ecoTEC plus combination boilers Connect the filling pipe as described in Section 5 4 2 Only in ecoTEC plus system boilers and in...

Page 32: ...setting of the operating mode dependent pump speed under the diagnostic number d 19 see section 8 1 2 5 8 Adjusting the by pass The appliances have an adjustable by pass valve The pressure can be adj...

Page 33: ...perating conditions The gas rate has been set during production and does not require adjustment The gas rate of the boiler should be checked with the front case fitted as follows Activate full gas rat...

Page 34: ...flash while the adjustment procedure is being carried out The available ranges of settings are given in Table 5 2 Push the i button for about five seconds or until the display stops flashing The value...

Page 35: ...Press i to activate the status indicator As soon as a heat demand is received the appliance runs through the status indicators S 1 to S 3 until the appliance is running correctly in normal mode and th...

Page 36: ...h the Gas Safety Installation and Use Regulations 1998 and the manufacturer s instructions In the UK CORGI registered installers undertake the work in compliance with safe and satisfactory standards A...

Page 37: ...maintenance instructions column 2 x 3 Check combustion by measuring CO and CO2 values compare to table 9 2 If the measurement is outside the tolerances follow the maintenance instructions column 2 If...

Page 38: ...valve Turn off the boiler CH service valves Loosen screw release the front case spring retaining clips located beneath the front edge of the appliance Remove the front casing by easing forward the bo...

Page 39: ...inegar 7 2 3 Checking the burner 1 Fig 7 4 Checking burner The burner 1 is maintenance free and needs no cleaning Check the burner surface for damage replace the burner if necessary After checking rep...

Page 40: ...correctly located 7 3 Cleaning the condensate siphon Danger Note that if the boiler is run with an empty condensate trap there is a danger that fumes might escape into the room and cause poison ing F...

Page 41: ...use the fault finding guide 1 Carry out electrical safety checks see section Preliminary Electrical Checks 2 Check that the external electricity supply to the boiler is on and a supply of 230 V is pre...

Page 42: ...g burner operation S 52 Water pressure 2 9 bar S 53 Appliance is within the waiting period of the operation block function due to water shortage VL RL spread too big S 54 Appliance is within the waiti...

Page 43: ...ext eBUS target value and target value terminal 7 d 10 Status internal heating pump 1 on 0 off d 11 Status external heating pump 1 to 100 on 0 off d 12 Cylinder charging pump via accessory module 1 t...

Page 44: ...0 adjustment range 99 to 0 d 58 From the third quarter of 2006 Activation of solar reheating Setting range 0 to 3 0 solar reheating disabled factory setting 3 activation of min hot water target value...

Page 45: ...es 80 to 83 If d 80 for example is selected only the first two digits of the number are displayed e g 10 The display switches to the last three digits e g 947 by pressing i In this example the number...

Page 46: ...ot inserted correctly on fan hall sensor defec tive fault in cable harness electronics defective F 49 eBUS undervoltage Short circuit on eBUS overload on eBUS or two power sources on eBUS with differe...

Page 47: ...listed below in this section may be carried out only by a qualified engineer Only use genuine spare parts for repairs Make sure the parts are correctly fitted and that their original position and alig...

Page 48: ...check see section 7 6 9 4 Replacing expansion vessel 1 2 3 4 Fig 9 4 Replacing expansion vessel Danger Before replacing the component comply with the safety instructions in Section 9 1 Disconnect the...

Page 49: ...nger Neither loosen nor retighten the four screws Fig 9 5 Pos 4 Caution Insert the seal rings for the flow and return pipe on the primary heat exchanger with a suitable lubricant Insert the flow and r...

Page 50: ...ch adjustment until the value stabilises Only for liquid gas Adjust only in very small increments approx 1 16 turn and wait approx 1 minute after each adjustment until the value stabilises Fold back t...

Page 51: ...51 Instructions for installation and servicing ecoTEC 839592_09 Appendix Appendix...

Page 52: ...Benchmark gas boiler commissioning checklist...

Page 53: ......

Page 54: ......

Page 55: ......

Page 56: ...839592_09 GB 05 2008...

Reviews: