4 Operation

8

Operating instructions ecoFIT sustain 0020277253_00

4.9

Setting the hot water temperature

Danger!
Risk of death from legionella.

Legionella multiply at temperatures below
60 °C.

Have a competent person inform you
about the measures that should be taken
to protect against Legionella in your in-
stallation.

Do not set any water temperatures below
60 °C without consulting the competent
person first.

1.

Press

(

).

The set hot water temperature flashes in the display.

Conditions

: No controller connected

Change the hot water temperature by pressing

or

.

Confirm by pressing

.

Conditions

: Controller connected

Use

to set the maximum possible hot water temper-

ature on the product.

Confirm by pressing

.

Set the required hot water temperature on the controller
(

Controller operating instructions).

4.10

Switching off the product's functions

4.10.1 Switching off heating mode (Summer mode)

1.

To switch off heating mode without switching off the hot
water generation, press

( ).

The value of the heating flow temperature appears
in the display.

2.

Use the

button to set the heating flow temperature to

Off

.

3.

Confirm by pressing

.

Heating mode is switched off.

The

symbol appears in the display.

4.11

Guaranteeing the correct filling pressure of
the heating installation

4.11.1 Checking the filling pressure of the heating

installation

Note

To ensure that the heating installation operates
smoothly, the filling pressure when the heating
installation is cold must be between 0.10 MPa and
0.20 MPa (1.0 bar and 2.0 bar) or lie between the
two dashed lines in the bar graph display.

If the heating installation extends over several
storeys, a higher filling pressure may be required
for the heating installation. Ask a competent per-
son for details.

In addition, the

symbol appears after approx.

one minute.

If the filling pressure in the heating installation
falls below 0.05 MPa (0.5 bar), then the product
switches off. The display alternates between the
fault message

F.22

and the current filling pres-

sure.

1.

Press

twice.

The values for the current filling pressure and for the
minimum and maximum filling pressures appear in
the display.

2.

Check the filling pressure in the display.

Result 1:

System pressure: 0.10 … 0.20 MPa (1.00 … 2.00 bar)
The filling pressure is in the intended pressure range.

Result 2:

Filling pressure: < 0.08 MPa (< 0.80 bar)

Fill the heating installation. (

Page 8)

If you have topped up the installation with suf-
ficient heating water, the display automatically
disappears after 20 seconds.

4.11.2 Filling the heating installation

Caution.
Risk of material damage due to heating
water that is extremely calciferous or cor-
rosive or contaminated by chemicals.

Unsuitable tap water damages the seals
and diaphragms, blocks components in the
product and heating installation through
which the water flows and causes noise.

Only fill the heating installation with suit-
able heating water.

1.

Ask a competent person where the filling cock is loc-
ated.

2.

Connect the filling tap to a heating water supply in the
way you were told by the competent person.

3.

Open all radiator valves (thermostatic radiator valves) of
the heating installation.

4.

Open the heating water supply.

Summary of Contents for ecoFIT sustain 618

Page 1: ...Operating instructions ecoFIT sustain 615 630 GB IE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 21 91 18 0 Fax 49 21 91 18 2810 info vaillant de www vaillant de ...

Page 2: ...itching on the product 7 4 8 Setting the heating flow temperature 7 4 9 Setting the hot water temperature 8 4 10 Switching off the product s functions 8 4 11 Guaranteeing the correct filling pressure of the heating installation 8 4 12 Protecting the heating installation against frost 9 4 13 Switching the product to standby mode 9 5 Troubleshooting 9 5 1 Detecting and rectifying faults 9 5 2 Callin...

Page 3: ...n unless they are supervised Any other use that is not specified in these in structions or use beyond that specified in this document shall be considered improper use Any direct use in industrial or commercial processes is also deemed to be improper Caution Improper use of any kind is prohibited 1 3 General safety information 1 3 1 Installation by competent persons only The installation inspection...

Page 4: ...the drain pipework to constructional conditions that may affect the operational reliability of the product 1 3 7 Risk of corrosion damage due to unsuitable combustion and room air Sprays solvents chlorinated cleaning agents paint adhesives ammonia com pounds dust or similar substances may lead to corrosion on the product and in the air flue pipe Ensure that the combustion air supply is always free...

Page 5: ...anel 50 1 9 8 7 6 2 3 4 1 5 1 Current heating flow temperature operating mode fault code or additional information 2 Current assignment of the right hand selection button 3 Left and right hand selection buttons 4 and button 5 Reset button 6 Maximum output only used for Austria Ger many and Switzerland 7 Access to the menu for additional information 8 Current assignment of the left hand selection b...

Page 6: ...ling mode Tmax Max flow temperature NOx NOx class for the product Code DSN Specific product code Information on the identification plate Meaning Read the instructions GC no Gas council number 3 5 Serial number The serial number is located on a plastic plate at the bottom of the front casing 3 6 CE label The CE label shows that the products comply with the basic requirements of the applicable direc...

Page 7: ...el contains information and setting options that you require as the end user The installer level is reserved for the competent person It is protected by a code Only competent persons may change any settings in the installer level 4 4 Cabinet type casing Enclosing the product in cabinet type casing requires compli ance with the applicable design instructions If you require cabinet type casing for y...

Page 8: ...20 MPa 1 0 bar and 2 0 bar or lie between the two dashed lines in the bar graph display If the heating installation extends over several storeys a higher filling pressure may be required for the heating installation Ask a competent per son for details In addition the symbol appears after approx one minute If the filling pressure in the heating installation falls below 0 05 MPa 0 5 bar then the pro...

Page 9: ...The display shows OFF and goes out The product is now in standby mode The product s frost protection function is activated The main power supply is not interrupted The product continues to be supplied with power 5 Troubleshooting 5 1 Detecting and rectifying faults If faults occur proceed in accordance with the table in the appendix Troubleshooting Page 11 If the fault cannot be eliminated using t...

Page 10: ...nt person permanently decommission the product 8 Recycling and disposal The competent person who installed your product is re sponsible for the disposal of the packaging If the product is labelled with this mark In this case do not dispose of the product with the household waste Instead hand in the product to a collection centre for waste electrical or electronic equipment If the product contains ...

Page 11: ...omfort protection mode flame loss at minimum load B Troubleshooting Fault Cause Measure Product does not start up No hot water Heating remains cold The gas isolator cock installed on site and or the gas isolator cock on the product is closed Open both gas isolator cocks The power supply in the building is disconnected Check the fuse in the building The product switches on automatically when the po...