5 Installation
16
Installation and maintenance instructions aroSTOR 0020290840_00
6.
Use the plug
(1)
to establish the connection to the elec-
tricity meter's control contact.
–
Twin-core cable: 0.75 mm
²
7.
Inform the end user if the product is controlled via the
low-tariff contact, so that any programming of operating
times does not conflict with the high- and low-tariff peri-
ods.
5.3.3
Controlling the fan externally
Condition
: Installing a partial pipe system
T degiv
T air
T eau
HP
X4
X3
X5
X2
2
1
1
2
▶
If you want to keep a room aerated permanently, even
when the product is switched off, you can connect the
contact of the external ventilator control system (fan
control).
Caution.
Risk of material damage caused by incor-
rect handling.
Only external control contacts are compat-
ible.
▶
Only connect the external control con-
tacts to potential-free contacts.
▶
In particular, do not connect any live
cables.
▶
Remove the covering hood.
▶
Remove the black protective cover from the PCB.
▶
Guide the cable through the grommet on the rear of
the product and through the grommet on the rear of the
electronics box.
▶
Connect the fan control cable to the plug
(2)
on the PCB
(1)
.
◁
Contact opened: Fan not running
◁
Contact closed: Fan running
▶
In the menu, set the "Fan with external control system"
mode to
FAN MODE
3.
5.3.4
Setting the fan speed
Validity:
aroSTOR VWL BM 200/5
OR aroSTOR VWL BM 270/5
If the unit is connected to a pipework system with lines that
are more than five metres long or smooth lines that are more
than ten metres long, the fan level must be adapted to en-
sure that the pressure losses that are caused by the air net-
work are offset. This change in level is implemented using
the unit's electronics box.
▶
Remove the covering hood. (
→
Page 11)
▶
Remove the covering hood from the PCB.
1
▶
Move the grey wire on the 5.5
µ
F capacitor
(1)
as shown
in the basic diagram opposite.
5.3.5
Connecting the photovoltaic installation
Condition
: Existing photovoltaic installation
This function can make use of the self-sufficiency optimised
by the photovoltaic installation to supply the heat pump and
the electrical immersion heater and to heat up the water in
the cylinder.
T degiv
T air
T eau
HP
X4
X3
X5
X2
2
1
2
1
1
Connection terminal 1
2
Connection terminal 2
Caution.
Risk of material damage caused by incor-
rect handling.
Only external control contacts are compat-
ible.
▶
Only connect the external control contacts
to potential-free contacts.
▶
In particular, do not connect any live
cables.
▶
Remove the covering hood.
▶
Remove the black protective cover from the PCB.