7 Handing the product over to the operator
18
Installation and maintenance instructions aroSTOR 0020290840_00
7
Handing the product over to the
operator
▶
Explain to the operator how the safety devices work and
where they are located.
▶
Inform the operator how to handle the product.
▶
In particular, draw attention to the safety information
which the operator must follow.
▶
Inform the operator of the necessity to have the product
maintained according to the specified intervals.
▶
Pass all of the instructions and documentation for the
product to the operator for safe-keeping.
▶
Inform the operator about measures taken concerning
the air pipe and inform them that they must not make any
changes.
8
Adapting the unit to the installation
8.1
Calling up the installer level
1.
Press the menu button.
2.
Turn the rotary knob until the
INST.MENU
menu ap-
pears in the display.
3.
Hold down the clock button and the menu button for
three seconds.
◁
The first menu item of the installer level
PV MODE
is displayed.
8.2
Optimising the unit's energy consumption
The domestic hot water generation can take place using a
back-up heater via the integrated heat exchanger.
7
8
9
10
11
N 12
Ph 13
14
15
Ph 1
N 2
N 3
Ph 4
Ph 5
N 6
1
1
Output 14-15
Caution.
Risk of destruction of the PCB.
If there is a voltage of 230 V at the floor-
standing boiler contact, there is a risk that the
PCB will be damaged.
▶
Measure the voltage before connecting.
▶
Remove the covering hood. (
→
Page 11)
▶
Remove the black covering hood from the PCB.
▶
Use a two-wire cable (each with a cross-section of 1.5
mm
²
to connect the potential-free contact between output
14-15 on the PCB of the thermodynamic water heater
and the back-up heater's thermostat input.
Note
The output alarm is not activated. It is conver-
ted to a control output for the floor-standing
boiler.
The end user can select either the electric
back-up heater or the floor-standing boiler
(e.g. summer or winter mode). The electric
back-up heater is selected by default.
8.3
Activating and setting photovoltaic mode
Condition
: Existing photovoltaic installation
▶
If the control for the photovoltaic installation is connected
to plug no. 1 and no. 2 on the product's PCB, you must
activate
PV MODE
.
◁
The electrical energy generated is stored in the form
of domestic hot water. You can set two efficiency
levels for the photovoltaic installation.
◁
PV ECO
= Low level of photovoltaic power gener-
ation. The heat pump generates an increased do-
mestic hot water temperature. The increased do-
mestic hot water temperature must be between the
normal domestic hot water temperature and 60 °C.
–
Factory setting: 60
℃
◁
PV MAX
= High level of photovoltaic power genera-
tion. The heat pump and the immersion heater gen-
erate an increased domestic hot water temperature.
The increased domestic hot water temperature must
be between the domestic hot water temperature of
the
PV ECO
mode and 65 °C.
–
Factory setting: 65
℃
▶
Turn the rotary knob to set the mode.
INST.MENU PV
MODE
◁
You can select which function has higher priority
(photovoltaic mode or frost protection/eco mode)
▶
Select
YES
.
▶
Press the rotary knob to confirm the selection.
▶
Press the menu button.
▶
Set the required domestic hot water temperature.
▶
Turn the rotary knob to set the priority.
INST.MENU
→
PV MODE
→
PRIORITY
.
◁
YES
: The signals from connection plugs no. 1 and
no. 2 have priority over the frost protection and eco
mode.
◁
no
: Frost protection and eco mode have priority over
the signals from connection plugs no. 1 and no. 2.