Installation 5
0020235301_03 uniSTOR Installation and maintenance instructions
11
5.2.6.1 High-level drain
Installing the highest drain is permitted as long as this does
not present a danger to anyone in or outside the building at
the drain point. Examples of points to consider when decid-
ing whether a location is suitable for the highest drain:
–
The possibility (taking the wind into account) that a per-
son might stay in the area where the water is drained
for a prolonged period of time, and, if this is the case,
whether the water is sufficiently cooled by that point to
pose no danger. The thermal conductivity of the material
surfaces, the climatic conditions, the installation location
and the drain pipework direction can, to different extents,
contribute to reducing the temperature of the water that is
being drained.
–
The position of the windows and other openings.
–
The probability of prams being under the drain opening.
–
The resistance of the surface to hot water.
–
The possibility of ice forming if water drains onto access
paths.
5.2.7
Installing the cylinder's temperature sensor
for the immersion heater
Note
The temperature sensor is used to control the
immersion heater via a multi-functional module
or a controller.
Condition
: With multi-functional module or controller
▶
Secure the temperature sensor.
5.2.8
Installing a secondary return
1
2
3
4
5
1
Cylinder
2
Non-return valve
3
Circulation pump
4
Secondary return pipe
5
Hot water outlet
1.
Carry out the installation in accordance with the schem-
atic drawing.
2.
Install an additional expansion vessel on the heating
return.
3.
If the secondary return is not installed, fit a plug on the
cylinder.
–
Diameter of the plug: 22 mm
5.2.9
Installing the thermostatic mixer
Condition
: Installation without secondary return
▶
Install the cylinder thermostatic mixer on the hot water
flow.
Condition
: Installation with secondary return
J
1
2
3
4
8
5
10
6
9
7
1
Expansion vessel
(Available as an ac-
cessory)
2
Tundish