5 Installation

10

Installation and maintenance instructions uniSTOR 0020235301_03

a T-piece for this. The pipe system must continuously
slope downwards, must be visible and must be protec-
ted against frost. There must be no risk of injury to per-
sons.

Diameter of the pipe: 22 mm

Length of the pipe between the temperature and
pressure relief valve and the expansion relief valve

(4)

(

Page 10):

600 mm

6.

Connect the cold water supply to the safety group

(2)

.

5.2.5

Installing an expansion vessel

1.

Install the expansion vessel close to the product.

2.

Install a pipe at the expansion vessel and connect the
terminal to the safety assembly

(6)

.

5.2.6

Installing a discharge pipe

≤ 600 mm

≥ 300 mm

D2

2

1

D1

1

Temperature and pres-
sure expansion relief
valve

2

Tundish

The drain connections of the temperature and pressure redu-
cing valve and the expansion relief valve must be connected
to the supplied tundish via 22-mm-thick copper pipes. The
tundish must be installed vertically, as close to the cylinder
as possible and with a maximum clearance of 600 mm from
the connection of the temperature and pressure reducing
valve. It must be installed in the same room as the cylinder,
but at a sufficient distance from electrical components. The
discharge pipes from the temperature and pressure reducing
valve and from the expansion relief valve can be connected
above the tundish using a T-piece. The discharge pipe from
the 28 mm connection of the tundish must consist of copper
pipes with a diameter of at least 28 mm and be connected to
a safe and visible drain point. The vertical section of pipe be-
neath the tundish must be at least 300 mm long before any
bends or diversions in the line. If the total resistance of the
drain line exceeds the values in the following table, you must
increase the diameter of the line. When installing the drain
line, comply with the standards, directives and laws that are
applicable in your country.

Size of
the outlet
valve

Minimum
diameter
of the
discharge
pipe D1

Minimum
diameter
of the dis-
charge
pipe from
the tun-
dish D2

Maximum
permiss-
ible res-
istance,
inform-
ation
on the
length of
a straight
pipe

Resist-
ance per
elbow or
bend

1/2"

15 mm

22 mm
28 mm
35 mm

9 mm

18 m

27 m

0.8 m
1.0 m
1.4 m

3/4"

22 mm

28 mm
35 mm
42 mm

9 m

18 m

27 m

1.0 m
1.4 m
1.7 m

1"

28 mm

35 mm
42 mm
54 mm

9 m

18 m

27 m

1.4 m
1.7 m
2.3 m

Sample calculation

The following example corresponds to a temperature and
pressure reducing valve G1/2 with a discharge pipe

(D2)

with

four 22 mm elbows and a length of 7 m from the tundish to
the drain point. According to the table, the maximum per-
missible resistance for a straight length of a 22-mm-thick
copper discharge pipe

(D2)

of a thermal expansion relief

valve G1/2 is 9.0 m. The resistance of the four 22 mm el-
bows, which are each 0.8 m in length, must be subtracted
from this, i.e. a total of 3.2 m. The maximum permitted length
is accordingly 5.8 m and is therefore below the current length
of 7 m. The calculation must therefore be performed using
the second largest size. The maximum permissible resist-
ance for a straight length of a 28-mm-thick pipe

(D2)

of a

thermal expansion relief valve G1/2 is 18 m. The resistance
of the four 28 mm elbows, which are each 1.0 m in length,
must be subtracted from this, i.e. a total of 4.0 m. The max-
imum permitted length is accordingly 14 m. As the current
length is 7 m, a 28 mm copper pipe

(D2)

should be selected.

A suitable location for the discharge pipe terminal is, for
example, beneath a fixed mesh above the odour trap in a
soakaway with a siphon. Low drain lines, for example up to
100 mm above external surfaces (car parks, meadows, etc.)
can be used provided that they are protected by a wire fence
or something similar to prevent children from coming into
contact with the waste water and provided that the system
is not visible. Do not install any valves or stop cocks on the
drain line.

Make sure that the discharge pipe from the tundish to the
drain has a constant downward gradient of at least 1:200.
The discharge pipe for the heat generator expansion relief
valve can be connected to the horizontal discharge pipe for
the cylinder behind the tundish using a T-piece.

Summary of Contents for 0010019234

Page 1: ...ation and maintenance instructions uniSTOR VIH S GB 500 BES GB IE Publisher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 492191 18 0 Fax 492191 18 2810 info vaillant de www vaill...

Page 2: ...stallation 8 5 1 Installing the product 8 5 2 Hydraulic connection 8 5 3 Electrical installation 12 6 Start up 15 6 1 Setting the immersion heater thermostat 15 6 2 Cold water inlet pressure 15 6 3 Se...

Page 3: ...tenance instructions for the product and any other system com ponents installing and setting up the product in ac cordance with the product and system ap proval compliance with all inspection and main...

Page 4: ...rrect tool 1 4 5 Risk of material damage caused by frost Do not install the product in rooms prone to frost 1 4 6 Risk of injury due to the heavy weight of the product Make sure that the product is tr...

Page 5: ...e Benchmark Checklist can be used to demon strate compliance with Building Regulations and should be provided to the customer for future reference Installers are required to carry out installation com...

Page 6: ...llation area Select a sensible installation site and take into consideration the routing of the pipework system Install the cylinder as close as possible to the heat generator in order to minimise hea...

Page 7: ...5 Check that the scope of delivery is complete Le gend point Quant ity Description 1 1 Expansion vessel 2 1 Tundish with retainer 3 1 Safety group 4 1 Documentation records 5 1 Domestic hot water cyli...

Page 8: ...dis cretion of the installer install a WRAS ap proved automatic air vent on the hot water outlet at the highest point 1 2 3 4 5 7 6 8 9 10 11 15 13 12 16 17 14 18 20 22 19 21 1 Cylinder draining poin...

Page 9: ...head so that it is facing upwards 5 2 3 Installing the drain valve The drain valve must be supplied by the customer Install the drain valve at the height of the cold water supply or further below this...

Page 10: ...pipe D1 Minimum diameter of the dis charge pipe from the tun dish D2 Maximum permiss ible res istance inform ation on the length of a straight pipe Resist ance per elbow or bend 1 2 15 mm 22 mm 28 mm...

Page 11: ...ability of prams being under the drain opening The resistance of the surface to hot water The possibility of ice forming if water drains onto access paths 5 2 7 Installing the cylinder s temperature s...

Page 12: ...the product 70 60 50 40 70 60 50 40 1 3 2 4 1 3 2 4 70 60 50 40 1 3 2 4 1 2 3 4 3 5 1 Immersion heater 2 Immersion heater ther mostat 3 Retainer for the temper ature sensor 4 Primary circuit thermo st...

Page 13: ...ectrics on the cylinder 2 Install a separate power supply for the immersion heater in accordance with the applicable standards 3 Use heat resistant cables for the immersion heater con nection Cable di...

Page 14: ...multi functional module 5 3 7 Connecting the control Condition eBUS The thermal cut out for the primary circuit is not used when connecting an eBUS unit Condition 230 V control If you use a 230 V cont...

Page 15: ...et the maximum value 6 4 Filling and purging the product Note It is not permitted to use valves or expansion relief valves for the purging 1 Check whether the drain valve is closed 2 Open the domestic...

Page 16: ...k page of these instructions If you require spare parts for maintenance or repair work use only the spare parts that are permitted for the product 9 Inspection and maintenance 9 1 Observing inspection...

Page 17: ...ion and maintenance instructions 17 11 Customer service To ensure regular servicing it is strongly recommended that arrangements are made for a Maintenance Agreement Please contact Vaillant Service So...

Page 18: ...ng 3 Thermostat set too high 4 Defective thermostat 1 Install a mixer tap 2 Repair the cable 3 Reduce the temperature of the thermostat to 55 C 4 Replace the thermostat Irregular domestic hot water ou...

Page 19: ...eating output solar circuit 19 2 kW Flow rate 900 l h Pressure loss in the heat exchanger heating circuit 10 mbar Volume of the heat exchanger heating circuit 23 l Volume of the heat exchanger solar c...

Page 20: ...SW GB 500 BES 3 way motorised valve 230 240 V 50Hz Thermostat 230 240 V 50Hz IP rating 21 Technical data Material VIH SW GB 500 BES Cylinder material Stainless steel 1 4521 Insulation material Glass...

Page 21: ...Appendix 0020235301_03 uniSTOR Installation and maintenance instructions 21 D Commissioning Checklist...

Page 22: ...UROV KDYH EHHQ WWHG LQ FRPSOLDQFH ZLWK 3DUW RI WKH XLOGLQJ 5HJXODWLRQV Yes Type of control system if applicable Y Plan S Plan Other Is the cylinder solar or other renewable compatible Yes No What is t...

Page 23: ...Date Engineer name Company name Telephone No Comments Signature SERVICE 05 Date Engineer name Company name Telephone No Comments Signature SERVICE 07 Date Engineer name Company name Telephone No Comme...

Page 24: ...product 16 E Electricity 3 F Filling and purging the heating circuit 15 Filling and purging the product 15 Filling and purging the solar circuit 16 Frost 4 H Handing over to the end user 16 I Identifi...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...byshire DE56 1JT Telephone 0330 100 3461 info vaillant co uk www vaillant co uk These instructions or parts thereof are protected by copyright and may be reproduced or distributed only with the manufa...

Reviews: