Set-up 4
0020188110_03 recoVAIR Installation and maintenance instructions
7
4.2.4
View from above
1457
499
31
4.3
Observing the requirements for the
installation site
4.3.1
Observing the requirements for the
product's installation site
The product can be installed in cellar spaces, storage or util-
ity rooms, and in attics. The product can be ceiling-mounted
or it can be wall-mounted.
▶
Observe the current applicable national construction reg-
ulations.
▶
Ensure that the installation site is dry and is frost-proof
throughout.
▶
Ensure that the installation site is aerated and ventilated.
▶
Install the supply air pipeline so that there is sufficient
distance to the exit air pipeline, exhaust air pipeline and
outflow purging.
▶
Check the load-bearing capacity of the wall or ceiling.
–
Load-bearing capacity:
≥
40 kg
▶
Check whether the supplied fixing elements are sufficient
for the selected installation site.
▶
Ensure that the installation site is not located higher than
max. 2000 metres above sea level.
Minimum clearances and installation clearances
400
400
600
▶
Observe the minimum clearances and installation clear-
ances when installing on the ceiling.
600
400
600
1
▶
Observe the minimum clearances and installation clear-
ances when installing on the wall.
▶
Plan sufficient space for installing the ventilation system.
▶
In order to minimise pressure losses, ensure that the dis-
tances between the header line of the ventilation system
and the product are as short as possible.
▶
After installation, ensure that the pipelines and the ventil-
ation system are easily accessible.
▶
Ensure that the mains plug/circuit breaker (depending on
the country) is always accessible after the installation.
▶
Ensure that there is sufficient space to install the con-
densate siphon and condensate drain pipework.
▶
If you install the product upright, the condensate dis-
charge
(1)
must point downwards.
▶
If the product is to be hidden behind panelling (suspen-
ded ceiling), make sure that it is accessible for mainten-
ance work through sufficiently large inspection openings.
Requirements for the protective areas
▶
Only install the product outside the protective areas
shown (0-2).
The height of the protective areas is limited by a horizontal
surface above the floor. The defined height is 225 cm. How-
ever, if a fixed shower head/water outlet is installed above
225 cm, this fixed shower head/water outlet limits the height
of the protective area.