4 Set-up
10
Installation and maintenance instructions recoVAIR 0020188110_03
90°
▶
Turn the display and the holder frame.
–
90°
▶
Place the holding frame into the cut-out in the operator
control screen.
▶
Place the display into the holding frame.
▶
Establish the cable connection at the display.
▶
Close the product. (
→
Page 11)
4.4.4
Connecting the condensate siphon/dry
siphon and condensate drain pipework
1.
Connect the condensate siphon/dry siphon to the
product (
→
Installation instructions for the condensate
siphon/dry siphon, accessories).
–
Condensate discharge pipe downward gradient
(descending from the product): > 5°
min. 20
1
A
B
Danger!
Risk of damage to health caused by incor-
rectly connected condensate drain pipe-
work!
In the interests of hygiene, the condensate
drain pipework must not be directly connec-
ted to the waste-water piping.
▶
Connect the condensate discharge to the
second siphon.
Caution.
Risk of material damage caused by con-
densate.
If a condensate discharge pipe has been con-
nected incorrectly, a build-up of condensate
and uncontrolled condensate drainage may
damage the product. Furthermore, the con-
densate may leak out of the product and onto
the floor.
▶
Install a drip distance of min. 20 mm
between the outlet for the condensate
drain pipework and the second siphon.
▶
Note the downward gradient for the con-
densate discharge pipe (> 5°).
2.
Connect the condensate drain pipework to the second
siphon while taking into consideration the drip distance
(1)
.