Ethernet Troubleshooting
Following are the advanced fault codes for the drive fault (F38) related to the option board. For more information,
see the X5 User’s Manual (Chapter 8). The
option board status LEDs
are described on
page 9
of this manual.
Table 9: Advanced Fault Codes
Advanced
Fault Code
Fault
Possible Cause
Corrective Measures
1
Option board loss
Option board is disconnected or
damaged
Check option board status LEDs,
ribbon cable connection, and
cycle power. Replace option
board if necessary.
2
Unstable ID during power-up
Option board hardware issues
Cycle power. If problem persists,
contact Vacon technical support.
3
Option board changed
Option board was changed during
last power-down
If the change was intentional,
cycle power.
4
Invalid ID
Option board hardware issues
Cycle power. If problem persists,
contact Vacon technical support.
5
Wrong or no daughter card
installed
Option DIMM module issues
Cycle power. If problem persists,
contact Vacon technical support.
6
Option board software error
Option board software issues
Cycle power. If problem persists,
contact Vacon technical support.
7
Option board removed
Option board was removed during
last power-down sequence
If the change was intentional,
cycle power. Otherwise, follow
corrective measures for fault
code 1.