START UP
vacon • 37
24-hour support: +358 (0)201 212 575 • Email: [email protected]
6.1.5.1
Monitoring menu
To enter the Monitoring menu from the Main menu, press the Push button Menu right when the lo-
cation indication M1 appears in the first line of the screen. The following figure shows how to view
the monitored values.
The monitored signals have the indication V#.# and are listed in the following table. Values are up-
dated every 0.3 seconds.
This menu is used only to verify the signals. Values can not be modified.
Code
Parameter
Min
Max
Unit
ID
Description
V1.1
Output power
0
1000
kW
1707
Output power of inverter, with compensated
LCL filter losses.
V1.2
Total energy kWh
0
4,29E+09
kWh
1837
Total energy of inverter fed into the grid.
V1.3
Energy today kWh
0
6553,5
kWh
1708
Energy fed into the grid today.
V1.4
Energy yesterday
0
6553,5
kWh
1733
Energy fed into the grid yesterday.
V1.5
DC voltage refer-
ence
50
150
%
1200
Used DC voltage reference by the regenerative
unit in % of the nominal DC voltage.
V1.6
DC-link voltage
0
1000
V
1839
Filtered DC-link voltage in Volt.
V1.7
Unit temperature
-50
200
°C
1109
Temperature of the unit in Celsius
V1.8
AC voltage
0
1000
V
1709
AC voltage measured on the grid side of the
main contactor by an external measurement
circuit.
V1.9
AC frequency
-60
60
Hz
1835
Grid frequency in Hz. The sign indicates the
phase order. Can be monitored only when
UNIT is in RUN state.
V1.10
Output current
0
Varies
A
1834
Output current of the inverter coming out of
the cabinet (transformers inside cabinet are
taken into consideration).
V1.11
Run time total [h]
0
99999999
h
1836
Total time the inverter has been running.
V1.12
Run time today
0
255
h
1731
The time the inverter has been running today.
V1.13
Run time yesterday
0
255
h
1732
The time the inverter ran yesterday.
V1.14
Grid connections
0
4,29E+09
1706
Total number of times the inverter has closed
the main contactor and connected to the grid.
V1.15
Standby remaining
0
65535
s
1201
Remaining time in standby mode, if standby
mode is activated.
Table 6-1. Monitoring values
RUN
READY
Local
M1
Monitor
V1
V14
RUN
READY
Local
V1.1
Output power
19.4 kW
RUN
READY
Local
V1.1
Daily energy
125 kWh