monitoring & parameters
vacon
•
47
5
P2.6
Parity type
0
2
0
813
0
= None
1
= Even
2
= Odd
The Stop Bit is 2-bit
When Parity type is
0
= None;
The Stop Bit is 1-bit
When Parity type is
1
= Even or
2
= Odd
P2.7
Communication time out
0
255
10
814
0
= Not used
1
= 1 sec
2
= 2 secs, etc
P2.8
Reset communication
status
0
1
0
815
When Canopen E6 board has been installed, the comm. parameters are as follows
V2.1
Canopen communication
status
14004
0
= Initialising
4
= Stopped
5
= Operational
6
= Pre_Operational
7
= Reset_Application
8
= Reset_Comm
9
= Unknow
P2.2
Canopen operation mode
1
2
1
14003
1
= Driver Profile
2
= Bypass
P2.3
Canopen Node ID
1
127
1
14001
P2.4
Canopen baud rate
1
8
6
14002
1
= 10 kbaud
2
= 20 kbaud
3
= 50 kbaud
4
= 100 kbaud
5
= 125 kbaud
6
= 250 kbaud
7
= 500 kbaud
8
= 1000 kbaud
When DeviceNet E7 board has been installed, the comm. parameters are as follows
Code
Parameter
Min
Max Default
ID
Note
Table 23: System parameters