24
•
vacon
monitoring & parameters
5
5.2 Quick setup parameters (Virtual menu, shows when par. 17.2 = 1)
Code
Parameter
Min
Max
Unit
Default
ID
Note
Motor nominal
voltage
180
690
V
Varies
110
Check rating plate on the
motor.
Motor nominal
frequency
30.00 320.00
Hz
50.00 /
60.00
111
Check rating plate on the
motor.
Motor nominal
speed
30
20000
rpm
1440 /
1720
112
Default applies for a 4-
pole motor.
Motor nominal
current
0.2 x
I
Nunit
2.0 x
I
Nunit
A
I
Nunit
113
Check rating plate on the
motor.
Motor cos
0.30
1.00
0.85
120
Check rating plate on the
motor.
Current limit
0.2 x
I
Nunit
2.0 x
I
Nunit
A
1.5 x
I
Nunit
107
Maximum motor current
Torque boost
0
1
0
109
0
= Not used
1
= Used
P2.1
Remote control
place 1 selection
0
2
0
172
0
= I / O terminal
1
= Fieldbus
2
= Keypad
Start function
0
1
0
505
0
= Ramp
1
= Flying start
Stop function
0
1
0
506
0
= Coasting
1
= Ramp
Min frequency
0.00
P3.2
Hz
0.00
101
Minimum freq reference
Max frequency
P3.1 320.00
Hz
50.00 /
60.00
102
Maximum freq refer-
ence
P3.3
Remote Control
Place 1 frequency
reference
selection
1
Varies
7
117
1
= Preset speed 0
2
= Keypad
3
= Fieldbus
4
= AI1
5
= AI2
6
= PID
7
= AI1 + AI2
8
= Motor potentiometer
9
= Pulse train / Encoder
10
= AIE1
11
= Temperature input 1
12
= Temperature input 2
13
= Temperature input 3
Table 5: Quick setup parameters
P1.1
P1.2
P1.3
P1.4
P1.5
P1.7
P1.15
P2.2
P2.3
P3.1
P3.2