Communications
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Message frame:
The reply to Preset Multiple Registers message is the echo of 6 first bytes.
Answer Slave - Master:
Reply frame:
Example 2:
In this example the actual speed and the first Process Data OUT variable of the drive is read. The
Process Data OUT registers 2103 and 2104 are read to achieve this. The Modbus function used to
read the values is 4 (Read Input Registers).
Read the Process Data 42103…42104 with command 4 (Read Input Registers).
Command Master - Slave:
Table 38.
01 10 07 D0 00 03
06 00 01
00 00 13
88 C8 CB
Table 39.
ADDRESS
01 hex Slave address 1 hex (= 1)
FUNCTION
10 hex Function 10 hex (= 16)
DATA
Starting address HI 07 hex Starting address 07D0 hex (= 2000)
Starting address LO D0 hex
No. of registers HI
00 hex Number of registers 0003 hex (= 3)
No. of registers LO
03 hex
ERROR
CRC HI
80 hex CRC 8085 hex (= 32901)
CHECK
CRC LO
85 hex
Table 40.
01 10 07 D0 00 03
80 85
Table 41.
ADDRESS
01 hex Slave address 1 hex (= 1)
FUNCTION
04 hex Function 4 hex (= 4)
DATA
Starting address HI 08 hex
Starting address LO 36 hex
No. of registers HI
00 hex Number of registers 0002 hex (= 2)
No. of registers LO
02 hex
ERROR
CRC HI
93 hex CRC field 93A5 hex (= 37797)
CHECK
CRC LO
A5 hex