Communications
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6.3
Modbus data mapping
6.3.1
Coils registers
A "coil" in Modbus is a single-bit binary data item which can be both read and written. In Vacon
®
100
the coils refer to some bits in the fieldbus control word." See page 33.
Table 14. Defined coil registers
6.3.2
Discrete inputs
A "discrete input" in Modbus is a single-bit binary data item which is read-only. In Vacon 100 the
discrete inputs refer to the fieldbus status word bits
.
Table 15. Defined Input Discrete
6.3.3
Holding registers and input registers
An "input register" in Modbus is a 16-bit value which is read-only. A "holding register" in Modbus is
a 16-bit value which can be both read and written. Holding and input registers are accessed using
different function codes, and the address ranges are different. In Vacon 100 the same information
can be accessed as input registers and holding registers, i.e. input register X refers to the same 16-
bit value as the holding register X.
The Modbus registers are mapped to the Vacon 100 drive as follows
Address
Function
Purpose
0001
RUN/STOP
Control Word, bit 0
0002
Direction
Control Word, bit 1
0003
Fault reset
Control Word, bit 2
Address
Function
Purpose
10001
Ready
Status Word, bit 0
10002
Run
Status Word, bit 1
10003
Direction
Status Word, bit 2
10004
Fault
Status Word, bit 3
10005
Alarm
Status Word, bit 4
10006
At reference
Status Word, bit 5
10007
Zero speed
Status Word, bit 6
10008
Flux ready
Status Word, bit 7