15

 

 

vacon

general data

Tel. +358 (0)201 2121 • Fax +358 (0)201 212205

7

- These instructions apply only to cases with one motor and one cable connection 

from the frequency converter to the motor.

- To fulfil standard EN61800-5-1, the protective conductor should be 

at least 10mm2 

Cu or 16mm Al

. Another possibility is to use an additional protective conductor of 

at least the same size as the original one.

Vacon 10 power ratings

* The maximum ambient operating temperature of Vacon 10-1L-0009 - 2 is 

+40°C!

Note: 

The input currents are calculated values with 100 kVA line transformer supply.

Mains voltage 208-240 V, 50/60 Hz, 1~ series

Frecuency converter 
type

Rated loadability

Motor 
shaft 
power

Nominal 
input current

Mechani-
cal size

100% contin. 
current I

N

 [ A ]

150% overload 
current [ A ]

P

[ kW ]

[ A ]

Vacon 10-1L-0001 - 2

1,7

2,6

0,25

4,2

MI1

Vacon 10-1L-0002 - 2

2,4

3,6

0,37

5,7

MI1

Vacon 10-1L-0003 - 2

2,8

4,2

0,55

6,6

MI1

Vacon 10-1L-0004 - 2

3,7

5,6

0,75

8,3

MI1

Vacon 10-1L-0005 - 2

4,8

7,2

1,1

11,2

MI2

Vacon 10-1L-0007 - 2

7,0

10,5

1,5

14,1

MI2

Vacon 10-1L-0009 - 2 *

9,6

14,4

2,2

15,8

MI3

Mains voltage 380-480 V, 50/60 Hz, 3~ series

Frecuency converter 
type

Rated loadability

Motor shaft 
power

Nominal 
input cur-
rent

Mechani
cal size

100% continu-
ous current 
I

N

  [ A ]

150% over-
load current 
[ A ]

380-480V sup-
ply

P[ kW ]

[ A ]

Vacon 10-3L-0001 - 4

1,3

2,0

0,37

2,2

MI1

Vacon 10-3L-0002 - 4

1,9

2,9

0,55

2,8

MI1

Vacon 10-3L-0003 - 4

2,4

3,6

0,75

3,2

MI1

Vacon 10-3L-0004 - 4

3,3

5,0

1,1

4,0

MI1

Vacon 10-3L-0005 - 4

4,3

6,5

1,5

5,6

MI2

Vacon 10-3L-0006 - 4

5,6

8,4

2,2

7,3

MI2

Vacon 10-3L-0008 - 4

7,6

11,4

3,0

9,6

MI3

Vacon 10-3L-0009 - 4

9,0

13,5

4,0

11,5

MI3

Vacon 10-3L-0012 - 4

12,0

18,0

5,5

14,9

MI3

Summary of Contents for 10

Page 1: ......

Page 2: ...s con nected to mains even if the motor is not running The control I O terminals are isolated from the mains poten tial However the relay output terminals may have a danger ous control voltage present...

Page 3: ...crew or DIN rail mounting Figure 1 Screw mounting left and DIN rail mounting right NOTE See the mounting dimensions on the back of the drive Leave free space for cooling above 100 mm and below 50 mm V...

Page 4: ...bles is 0 5 0 6 Nm Figure 3 Vacon 10 power connections MI1 Figure 4 Vacon 10 power connections MI2 MI3 1 230V 3 400V Motor out MAINS MOTOR Strip the plastic cable coating for 360 earthing L1 L2 N L3 U...

Page 5: ...pport 358 0 40 837 1150 Email vacon vacon com 2 2 2 2 Control cabling Figure 5 Open the cover Figure 6 Install the control cables See next page Strip the plastic cable coating for 360 earthing Control...

Page 6: ...Vacon 10 RS 485 I O terminals Terminal Signal Factory preset Description 3 GND I O signal ground 6 24Vout 24V output for DI max load 50 mA 7 GND I O signal ground 8 DI1 Digital input 1 1 Start forward...

Page 7: ...indicate the status of the drive provide the user with information on faults and help the user to select the control place or fieldbus address Figure 1 The status LEDs of Vacon 10 RS 485 The followin...

Page 8: ...switch is in STOP posi tion 5 Connect the drive to mains 6 This step is not valid for API RS 485 7 Perform test run without motor see the User Manual at www vacon com 8 Run no load tests without motor...

Page 9: ...When keypad is selected as the control place Vacon RS 485 starts forward when the START button is pressed The frequency reference can be increased for 5Hz with each press of the button Green Green Red...

Page 10: ...ddress selection The slave addresses are binary coded and indicated with blinking LEDs Press the STOP button to move to the next address 4 Address 1 Address 2 Address 3 Address 4 Address 5 Address 6 A...

Page 11: ...of the motor M1 6 Motor power 5 Calculated actual nominal power of the motor M1 7 Motor voltage V 6 Motor voltage M1 8 DC link voltage V 7 Measured DC link voltage M1 9 Unit temperature C 8 Heat sink...

Page 12: ...nit 107 P1 15 Torque boost 0 1 0 109 0 Not used 1 Used P2 1 Control place 1 3 3 125 1 I O terminal 2 Keypad 3 Fieldbus P2 2 Start function 0 1 0 505 0 Ramp 1 Flying start P2 3 Stop function 0 1 0 506...

Page 13: ...r of error messages yyy 0 999 Number of good messages S2 2 Fieldbus protocol 0 1 1 809 0 FB disabled 1 Modbus S2 3 Slave address 1 255 810 S2 4 Baud rate 0 5 5 811 0 300 1 600 2 1200 3 2400 4 4800 5 9...

Page 14: ...rt pulse long pulse Red LED blinking sequence Fault code Fault name 1 Overcurrent 2 Overvoltage 3 Earth fault 8 System fault 9 Undervoltage 13 Frequency converter undertempera ture 14 Frequency conver...

Page 15: ...torage temperature 40 C 70 C Enclosure class IP20 Relative humidity 0 95 RH non condensing non corrosive no dripping water Altitude 100 load capacity no derating up to 1000m 1 derating for each 100m a...

Page 16: ...0 contin current IN A 150 overload current A P kW A Vacon 10 1L 0001 2 1 7 2 6 0 25 4 2 MI1 Vacon 10 1L 0002 2 2 4 3 6 0 37 5 7 MI1 Vacon 10 1L 0003 2 2 8 4 2 0 55 6 6 MI1 Vacon 10 1L 0004 2 3 7 5 6 0...

Page 17: ......

Page 18: ...Bentsrudveien 17 3080 Holmestrand telephone 47 330 96120 fax 47 330 96130 romania Vacon Romania Reprezentanta Cuza Voda 1 400107 Cluj Napoca Tel 40 364 118 981 Fax 40 364 118 981 russia ZAO Vacon Driv...

Reviews: