PARAMETER
VALUE
DESCRIPTION
AntE SCor
MEMO
St.AP
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the opening phase
PAUS PAUS
PAUS
The gate stops and goes to pause
ChiU
The gate immediately starts closing
no
The gate go on with the opening phase (command is ignored)
St.Ch
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase
StoP StoP
StoP
The gate stops and its cycle is considered as finished
APEr
The gate opens again
St.PA
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a
Start command when the gate is open during its pause phase
ChiU ChiU
ChiU
The gate starts closing
no
Command is ignored
PAUS
The pause time is reset (
Ch.AU
)
SPAP
Pedestrian Start during the partial opening phase
This menu allows fixing the control unit conduct in case it receives a
Pedestrian Start command during the partial opening phase.
m
WARNING
: a Start command in any phase of partial opening
will cause the total opening; the Start Pedestrian command is always
ignored during a total opening.
PAUS PAUS
PAUS
The gate stops and goes to pause
ChiU
The gate immediately starts closing
no
The gate goes on with the opening phase (command is ignored)
Ch.AU
Automatic closing
no
no
no
Function deactivated
0.5” - 20.0’
The gate closes after the setup time
Ch.tr
Closing after transit
This function allows having a fast closing as soon as transit through
the gate is completed, therefore, a time shorter than
Ch.AU
is
generally used
no
no
no
Function deactivated. The gate closes after the time set for the
function
Ch.AU
0.5” - 20.0’
The gate closes after the setup time
PA.tr
Pause after transit
In order to let the gate open for the shortest possible time, it is
possible to stop the gate once the passage before the photocells is
detected.
If the automatic working is enabled, the time of the pause is
Ch.tr
.
no
no
no
Function deactivated
Si
Function activated