page G
Programming NB 3000 Nivobob
40051
M_START
Start of a measurement
Start
1
Note: The Modbus master must set the register back to 0 after the measurement has started.
The started measurement is indicated as “Busy” in the M_STATUS register
W
40046
M_DISTANCE
Actual measured distance, in mm
Note: After the unit has finished the measurement, the M_STATUS register states “Ready,
measurement valid” (the Modbus master must read the M_STATUS register).
Then the data on the register M_DISTANCE is valid.
R
40055
M_VOLUME
Actual measured volume (considering the programmed cone height), in ‰
See note on register M_DISTANCE
R
40052
M_INHIBIT
Block command (allows to block the unit, so that no measurement can be started)
No block
0
Block
1
The unit will remain blocked as long as the register has the value “Block”.
Note: Unit states the blocked status through the M_ STATUS register.
W
0
40045
M_STATUS
States the functional status of the unit
Blocked
1
Ready, measurement not valid
2
Ready, measurement valid
6
Busy
8
Failure present
16
Temporary not ready
32
-> Explanation see next page
R
Measurement
Modbus Register
The following registers describe the communication via Modbus.
CAUTION
Writing to the registers different from what is stated will cause a miss function of the unit
Setup
Register
address
Register
name
Register
description
Register
use
Default
value
40001
M_LANGUAGE
Language on the menu
DEUTSCH
0
ENGLISH
1
FRANCAIS
2
RUSSIAN
3
R/W
0
40002
M_UNIT
Unit used for distance visualisation
METER
0
FEET
1
R/W
0
40003
M_MAX_MOVE_DIST
Max. move distance mm
R/W
1000
40004
M_SILO_HEIGHT
Silo height
mm
R/W
0
40005
M_AIR_DIST
Air distance
mm
R/W
0
40006
M_CONE_HEIGHT
Cone height
mm
R/W
0
40022
M_TIMER
Timer interval (for automatic start of measurements) , in 1/100 hours (Off = 0)
Notes:
1/100 hour = 36 sec
Minimum time for standard motor: 0,10 hours (value =10)
Minimum time for brushless motor: 0,05 hours (value = 5)
R/W
0