Continuous level measuring system
NB 3000
Technical information / Instruction manual
page G
Programming NB 3000 Nivobob
Advanced menus
(use only if necessary)
With the advanced menues it is possible to set the outputs and to display the actual state of the unit.
Entering the advanced menues:
If the unit is working in normal operation (measurement mode), press both "arrow" buttons together for approx. 2 seconds.
Measurement mode
0,0m (0,0ft)
Output Adjustment menu
Press both
buttons together
for 2 seconds
Diagnostics menu
Communication menu
Press to return to
measurement mode
Entering into the Output Adjustment menu
(see page G26)
Entering into the Diagnose menu
(see page G29)
Entering into the Communication menu
(see page G31)
To reset all programmed parameters to factory setting (default values), press the buttons ARROW UP, ARROW DOWN and SETUP together for
approx. 10 seconds.
Programming buttons
Continues with next adjustment item
Continues with measurement display after parameter adjustment
Starts measurement
Cancels a Failure or Maintenance message
Increases the value to be adjusted
Decreases the value to be adjusted
Factory settings
Runtime messages
During measurement mode, following runtime indications are given:
*
Upper Stop Position is reached
Motor is moving the sensor weight downwards resp. upwards (fast mode)
Motor is moving in slow mode (shortly after motor start and before Upper Stop Position
is reached)
Measurement interruption is active (terminal 24-26 not connected, see page G22)
Measurement interruption is active (signal is set via Modbus or Remotebox NB 9000,
see also page G35)
Note:
Pressing the ARROW DOWN
button in measurement
mode brings up more service
information (not described in
this manual
Blocked 24-26 open
Blocked Modbus