Level limit switch
Series CN 4000
Technical Information / Instruction manual
page
Notes for use in Hazardous Locations
Zone classification
General Notes
Marking
Devices with Ex approval are marked on the name plate.
Process pressure
The device construction allows process over-pressure upto 6/ 16 bar (87/ 232 psi) (see name
plate). These pressures are allowed for test purposes. The definition of the ATEX/ IEC-Ex is only
valid for a container-over-pressure between -0.2 .. +0.1 bar (-2.9 .. +1.45 psi). For higher or lower
pressures the approval is not valid.
Process and ambient
temperature
The permitted temperature ranges are marked on the name plate. Observe derating curves.
Permitted zones (categories) for mounting in partition wall
EPL (IEC-Ex)
Db
Category (ATEX)
2D
Zone
21
EPL (IEC-Ex)
Da
Category (ATEX)
1D
Zone
20
Max. Surface Temperature
The temperature marking on the name plate refers to the instruction manual. On the following tables the relevant
temperature ratings are shown. The maximum surface temperature is the hottest temperature of the unit which could occur during
malfunction (according to Ex-definition).
Max.
ambient
temperature*
Max. process
temperature*
Max. surface
temperature
60°C (140°F)
CN 4020: 120°C (248°F)
CN 4030: 110°C (230°F)
120°C (248°F)
CN 4050: 80°C (176°F) 135°C (275°F)
Version CN 4020 120°C/ CN 4030/ CN 4050:
Usable in
zone
ATEX
category
IEC-Ex
Equipement Protection
Level (EPL)
Dust applications 20, 21, 22
1 D
Da
* in case of conductive dust
additional demands for the
installation are possible.
21, 22
2 D
Db
22
3 D*
Dc
Ambient
Process
Max.
ambient
temperature
Max. process
temperature
Max. surface
temperature
60°C (140°F)
120°C (248°F)
130°C (266°F)
140°C (284°F)
150°C (302°F)
160°C (320°F)
170°C (338°F)
180°C (356°F)
120°C (248°F)
130°C (266°F)
140°C (284°F)
150°C (302°F)
160°C (320°F)
170°C (338°F)
180°C (356°F)
Version CN 4020 180°C:
* Observe derating (see page 7)
Capanivo
®
1
2
3
4
5
6
7
8
9
10
11
12
CN 4000
gi011217