Level limit switch
Series CN 4000
Technical Information / Instruction manual
page
Mounting
General Safety Instructions
Process
pressure
Improper installation may result in loss of process pressure.
Chemical resistance
against the medium
Materials of construction are chosen based on their chemical compatibility (or inertness) for general
purposes. For exposure to specific environments, check with chemical compatibility charts before
installing.
Fastening of the
threaded process
connection
Mounting torque for the thread may not exceed 40 Nm (metal thread)/ 20 Nm (plastic thread). Use a
open-end wrench. Do not fasten by turning the housing, for this will destroy the unit.
Food grade material
The materials are available for the use under nornal and predictable applications (according to directive
1935/2004 Art.3). Other conditions can influence the safety.
Mounting instructions
Direction of the cable
glands
When the unit is mounted from the side, ensure, that the cable glands face downwards and are closed
to avoid water penetration into the housing. The housing can be rotated after installation.
Sealing
Ensure proper seal of the process thread in case of process pressure.
CORRECT
Probe leads
into the product
WRONG
Socket too long
Observe min. distance between two sensors, to
metal silo wall and to protective angle.
Distances of the probe
Oblique
mounting
Observe mounting angle to
ensure, that the active tip
of the probe has enough
distance to the metal silo wall
Capanivo
®