Jack Jumper
®
Cutout Bypass Tool
Product Description
The Jack Jumper
®
Cutout Bypass Tool permits a safe and quick method to
bypass an overhead cutout without the tedious use of bulky jumper cables. The
tool is indispensable for fuse coordination tasks and permits easy bypass of an
underground dip. The Jack Jumper
®
Cutout Bypass Tool saves time and money,
eliminates risk of service interruption and prevents accidental cross phasing.
The primary purpose of the Jack Jumper
®
Cutout Bypass Tool is to temporarily
bypass a cutout fuse door during fuse coordination. The Jack Jumper
®
Cutout
Bypass Tool is rated at 100 Amps continuous AC current without exceeding a
40°C temperature rise. It is used to bypass cutouts on both overhead lines and
underground taps.
For 200 Ampere SMD-20 Power Fuses attach a Jack Jumper
®
Cutout Bypass Tool
on each side (this only works for SMD-20 Power Fuse Tools and cannot be utilized
for standard cutouts).
Installation and removal of the Jack Jumper
®
Cutout Bypass Tool is done with a
shotgun stick.
USJJ-007 38 kV SMD-20 Power Fuse Bypass Tool
!
!
WARNING
Carefully read and fully understand the INSTRUCTION
MANUAL prior to operating, maintaining or testing this device.
Improper operation, handling or maintenance of this device
can result in death, grievous personal injury and or equipment
damage.
!
!
WARNING
Follow safe work procedures and practices when utilizing this
device. Failure to use this device in a safe manner can result
in death, grievous personal injury and or equipment damage.
!
!
WARNING
These instructions are not intended to replace or be a
substitute for proper safety training procedures. Failure
to select the proper tool in regards to minimum system
requirements can result in death, grievous personal injury and
or equipment damage.
!
!
WARNING
Only trained and qualified personnel should operate, inspect
and maintain this device.
!
!
WARNING
Only install the Jack Jumper
®
Cutout Bypass Tool with the use
of an insulated shotgun stick. When attaching or detaching
the Jack Jumper
®
Cutout Bypass Tool do not use abrupt or
rough movements, be gentle and do not hurry.
!
!
WARNING
If you are servicing a fuse, replace the fuse as quickly as
possible. The fuse is a protective device. The Jack Jumper
®
Cutout Bypass Tool DOES NOT FUNCTION AS A FUSE.
If you must leave the area, replace any fuses and remove
the Jack Jumper
®
Cutout Bypass Tool. It is not a fuse
replacement or permanent by-pass mechanism.
!
!
WARNING
Never install or remove a Jack Jumper
®
Cutout Bypass Tool
on an open cutout.
Perpendicular Ring
Spring
Mechanism
In-Line Ring
Attachment Hook
Attachment Hook