39
P/N
240011589
, Rev. A [08/03/2016]
APPENDIX A - CONTROL MODULE
x
Recheck ignition sequence as follows.
— Reconnect main valve wire.
— Adjust thermostat above room temperature.
— Verify ignition sequence at burner.
— If spark does not stop after pilot lights, replace
module.
— If main burner does not light or if main burner lights
and system locks out, check module, ground wire and
gas control as described in troubleshooting table. See
Table 9, Page 35.
Figure 19 - Pilot Flame
Correct Pilot Flame: 3/8 to 1/2 inch in flame.
See Figure 15, Page 27.